Controls

39

RT-SVX20A-E4

Remote potentiometer

To install the remote potentiometer,
cut the jumper WL on the
economizer ECA board, and connect
the wires to J11 and J12.

Note: This potentiometer allows to
adjust the permanent fresh air
intake from 0 to 50%.

0 W corresponds to closed fresh air
damper.

270 W corresponds to 50% open
fresh air damper.

Figure 21 - Remote potentiometer dimensions

Figure 22 - Remote potentiometer wiring

1 = Remote potentiometer
2 = ECA Board
WH = White wire
RD = Red Wire
BU = Blue wire
_____ Factory wiring
------- Field wiring