Operation, Unit start-up – Trane Voyager 1 Rooftop Unit TSD User Manual

Page 54

Advertising
background image

Operation

RT-SVX20A-E4

54

Unit start-up

Verification of gas valve settings -
(Reserved for the qualified gas
technician)

WARNING! Improper gas valve
setting may lead to burner
destruction and people injury.

Note: Unit factory-set for G20.

Figure 32 - Gas valve

1 = Screw to set gas valve

1

3/32"

G20 - 7.5mbar

G20 - 7.5mbar
G25 -10.5mbar

G25 -10.5mbar

1

3/32"

Note: Unit to be installed outside
only.

Note: Expansion valve must be
adapted to the type of gas used:

G 20: 20 mb

G 25: 25 mb

G 31 (Propane): 37 or 50 mb

Table 50 - Gas type designation per country

Table 51 - Gas burner data

Notes:
(1) G20 heating output given for 34,02 MJ/m

3

(15°C-1013)

(2) G25 heating output given for 29,30 MJ/m

3

(15°C-1013)

(3) G31 heating output given for 46.34 MJ/kg

Burner

G120

G200

G250

Gas Type

G20

G25

G31

G20

G25

G31

G20

G25

G31

Heating Input (kW)

0,0

0,0

0,0

0,0

0,0

0,0

0,0

0,0

0,0

Heating Output (kW)

24,6

25

25,1

41,3

41,7

41,9

51,9

52,3

52,6

Efficiency

93%

93%

93%

93%

93%

93%

#DIV/0!

#DIV/0!

93%

Gas Flow rate (Nm

3

/h)

2,8

3,3

2,1

4,7

5,5

3,5

5,9

6,9

4,4

Specific Heating Capacity (MJ/kg)

34,02

29,3

46,34

34,02

29,3

46,34

34,02

29,3

46,34

Heating Output per stage (1st/2nd) (%)

0%-100%

0%-70%-100%

0%-70%-100%

Inlet pressure Min/Nominal/Max (mbar)

17 / 20 / 25

20 / 25 / 30

25 / 37 / 45

17 / 20 / 25

20 / 25 / 30

25 / 37 / 45

17 / 20 / 25

20 / 25 / 30

25 / 37 / 45

Low pressure switch setting (mbar)

15

15

20

15

15

20

15

15

20

Manifold pressure (mbar)

7,5

10,5

24,9

7,5

10,5

24,9

7,5

10,5

24,9

No of injectors

3

4

5

Injector size (Drill / mm)

(33) / 2.87mm

(51) / 1.70mm

(1/8") / 3.175mm

(49) / 1.85mm

(1/8") / 3.175mm

(49) / 1.85mm

Smoke analysis

Gas / Voltage

G20 - 20mbar

400/3/50

G25 - 25mbar

400/3/50

G31 - 37mbar

400/3/50

G20 - 20mbar

400/3/50

G25 - 25mbar

400/3/50

G31 - 37mbar

400/3/50

G20 - 20mbar

400/3/50

G25 - 25mbar

400/3/50

G31 - 37mbar

400/3/50

CO %

0.0012%

0.0017%

0.0003%

0.0020%

0.0015%

0.0011%

0.0020%

0.0015%

0.0011%

Nox ppm

59 ppm

44 ppm

8.7 ppm

10 ppm

10 ppm

11 ppm

10 ppm

10 ppm

11 ppm

CO

2

%

8,29%

9,20%

8,90%

7,10%

7,10%

8,28%

7,10%

7,10%

8,28%

Destination countries

Pressure in mbar

Category

FR

20/25 37

II2E+3P

DE-LU-PL

20

I2E

CH-ES-GB-IE-PT-CZ-GR

20 37

II2H3P

NL

25 30

II2L3P

IT-AT-NO-FI-SE-EE-LT-LV

20

I2H

IT

28-30/37

I3+

BE

20/25

I2E

DK-SK-SI-TR

20

I2H

BE-PL

37

I3P

AT-DE-LU-HU-SK

50

I3P

HU

25

I2H