Model Number

T90S3S08KS6XSN

T90S3S10KS6XSN

T90S3S16KS6XSN

T90S3S22KS6XSN

Capacity

KVA/KW

80/72

100/90

160/144

225/202.5

Topology

True On-Line, Double Conversion, Advanced Multi-Level IGBT Technology

Input

Voltage

480 V, Three-Phase, Three-Wire + Ground/Bypass Input, 480 V, Three-Phase, Three-Wire + Ground

Voltage Range

480 V, -20% to +15% (384 to 552 V Without Utilizing Battery)

Power Factor

Greater than 0.99

Current THD

<3% at 100% Load (No Input Filter Required)

Frequency

60 Hz (± 10%)

Output

Voltage

480 V, Three-Phase, Three-Wire + Ground

Frequency

60 Hz, ±0.01% (In Free-Running Mode)

Voltage Regulation

±1.0% (0.5% Typical)

Power Factor

0.9 Lagging

Power Factor Range

0.9 to 1.0 Lagging

Voltage THD

<2% for Linear Load, <5% for Non-Linear Load

Overload (Inverter)

125% for 2 Minutes; 150% for 60 Seconds

Overload (Bypass)

1000% for One Cycle

Battery

DC Link

480 VDC

Ripple Voltage

±0.23%

±0.29%

Environment

Temperature Range

32° to 104°F (0° to 40°C)

Relative Humidity

5% to 95% Non-Condensing

Heat Rejection

11,307 BTUs/Hour

14,133 BTUs/Hour

19,408 BTUs/Hour

27,292 BTUs/Hour

Efficiency (Full-Load)

95.6%

95.6%

96.5%

96.5%

Efficiency (20% Load)

92.5%

92.5%

94.6%

94.7%

Altitude

7380 Feet Maximum Without Derating (2250 Meters)

Audible Noise

69.5 dBA at 1 Meter

Dimensions

Dimensions (W x D x H)

27.6 x 32.8 x 80.6 in.

(700 x 832 x 2047 mm)

35.4 x 32.8 x 80.6 in.

(900 x 832 x 2047 mm)

Weight

835 lbs. (388 kg)

855 lbs. (388 kg)

1160 lbs. (526 kg)

1230 lbs. (558 kg)

Features

Digital Signal Processor (DSP) Control, Fully Digital IGBT Converter & Inverter, High Efficiency Over Wide Load Range,

Transformer-Less Design, N+1 and N+N (Up to Four in Parallel) Capability, Dual-Input Feed, Electronic Battery Isolation,

RS232 and Dry Contact Interface, Small Footprint, Lightweight Design

Standards

UL 1778, CUL, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), FCC Class A, Article 47, Part 15.B

Warranty

Three Years Onsite (Optional Two Year Extended Warranty)

See Toshiba Warranty Policy for Full Details

Service

24-Hour, 365-Day Technical Support 1-877-867-8773

UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC

INDUSTRIAL DIVISION

13131 West Little York Road, Houston, Texas 77041
Tel 713/466-0277 Fax 713/466-8773
US 800/231-1412 Canada 800/872-2192 Mexico 001/800/527-1204
www.toshiba.com/ind
Copyright 12/2008 UPS G9000 B05 23 08-001

Available Through:

*UPSg9000MMCT081209*

G9000 Series 80/100/160/225 KVA UPS

Battery

Cabinet

ac/dc IGBT

converter

dc/ac IGBT

Inverter

Static Transfer Switch

G9000 Series UPS Module

AC Output

480 Vac

Three-Phase,

Three-Wire with

Ground

AC Input

480 Vac

Three-Phase,

Three-Wire with

Ground

Bypass Input

480 Vac

Three-Phase,

Three-Wire with

Ground

dc/dc IGBT

chopper

Optional Jumper for Single-Source Input

Two G9000 UPS Modules in

Parallel Configuration

ac
OUTPUT

TIE

caBINET

ac

INPUT

UPS #1

UPS #2