Outdoor Unit

Installation Manual

EN

7

ELECTRICAL CONNECTIONS

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in
personal injury or death.
• The unit cabinet must have an uninterrupted or

unbroken ground to minimize personal injury if an
electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes.

• Before performing service or maintenance, be sure

main power switch is turned OFF.

CAUTION

All wiring and connections must comply with NEC, CEC,
local codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage
or improper operation.
• Unit failure as a result of operation on improper line

voltage or excessive phase imbalance constitutes
abuse and may cause damage to electrical
components.

• Wrong wiring may cause a burn-out of some electrical

parts.

• Do not damage or scratch the conductive core or inner

insulator of the power and inter-connecting wires
when peeling them.

„

Field wiring

The dashed lines show field wiring.

• System interconnection wire size must be AWG12.
• Breaker must have a capacity specified in the

following table.

• All wiring must comply with local electric codes and

NEC (National Electric Code) or CEC (Canadian
Electric Code).

• Connect the system interconnection wires (indoor to

outdoor) to the identical terminal numbers on the
terminal block of each unit.
Incorrect connection may cause a failure.

1. With the front panel removed the electrical control

box is exposed at the top right corner of the unit.

2. Terminate the field wiring conduit (if used) at the

conduit connection holes provided.

3. Route the field power wires and the system

interconnection wires as shown on the following
pages. Terminate the wires at field wiring terminal
blocks located immediately below the electrical
control box.

Electric parts box

Conduit connection
holes

Piping knockout

Pipe cover

Front pane

Electric control box

Field wiring

terminal

blocks

Conduit connection

holes

Front panel

Piping knockout

Front Pipe cover

Valve mounting

bracket

Model RAV-

SP240

Power supply

208/230 V, 60 Hz

MCA

24 A

MOCP (MAX Fuse/CB)

40 A

Breaker

25 A

System interconnection wires

AWG12

MCA = Minimum Circuit Amps

MOCP =Maximum Over Protection Device Amps.

L

1

L

2

L

1

L

2

S

L

1

L

2

S

Input

power

(Field power

supply)

(System

interconnection wires)

ground

Outdoor unit

Indoor unit

Remote

controller

circuit breaker

208/230 V~,

60 Hz

14-EN