Evacuate and dehydrate the system, System vacuum and charge, Caution – Toshiba CARRIER RAV-SP240AT2-UL User Manual

Page 18

Advertising
background image

Toshiba

– 17 –

Outdoor Unit

Installation Manual

8

EVACUATE AND DEHYDRATE THE

SYSTEM

CAUTION

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor heat exchanger should
be evacuated using the recommended deep vacuum
method of 500 microns. The alternate triple evacuation
method may be used if the procedure outlined below is
followed. Always break a vacuum with dry nitrogen.

„

SYSTEM VACUUM AND
CHARGE

Using Vacuum Pump

1. Completely tighten flare nuts A, B, C, D, connect

manifold gage charge hose to a charge port of the
low side service valve.

2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage.

4. Start vacuum pump.
5. Evacuate using either deep vacuum or triple

evacuation method.

6. After evacuation is complete, fully close the low side

of manifold gage and stop operation of vacuum
pump.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump
capable of pulling a vacuum of 500 microns and a
vacuum gage capable of accurately measuring this
vacuum depth. The deep vacuum method is the most
positive way of assuring a system is free of air and
liquid water.

Triple Evacuation Method

The triple evacuation method should only be used
when vacuum pump is only capable of pumping down
to 28 in. of mercury vacuum and system does not
contain any liquid water.
Refer to “Triple Evacuation Method chart” and proceed
as follows:
1. Pump system down to 28 in. of mercury and allow

pump to continue operating for an additional 15
minutes.

2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system

and open until system pressure is 2 psig.

4. Close service valve and allow system to stand for 1

hr. During this time, dry nitrogen will be able to
diffuse throughout the system absorbing moisture.

5. Repeat this procedure as indicated in the chart.

System will then be free of any cotaminants and
water vapor.

Service Valve

Indoor Unit

C

D

A

B

Refrigerant

Low Side

High Side

Outdoor Unit

Service Valve

Manifold

500 microns

Manifold Gage

Low side valve

Charge hose

High side valve

Charge hose

Vacuum pump

Low side valve

500

0

1000

1500

2000

2500

3000

3500

4000

4500

5000

1

2

3

4

5

6

7

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT DRY

SYSTEM

Deep Vacuum Graph

MICRONS

MINUTES

17-EN