Problem

Possible Cause

Remedy

Unit runs but

Inadequate airflow at

Remove items blocking

produces very

the front of the unit

airflow

little ice

Ice thickness

Adjust ice thickness.

(continued)

adjustment dial

See ADJUSTING ICE

improperly set

THICKNESS

Ice is slow to

Ice-making system

Run unit through

release or does

is dirty

automatic clean cycle.

not release from

See CARE AND

the evaporator

CLEANING

Unit is not level

See LEVELING THE UNIT

Low air temperature

Surrounding air

around unit

temperature must be
at least 50°F (10°C)

Poor ice quality

Poor incoming water

Consult a qualified

(soft or unclear)

quality

plumber to test the
water quality and
recommend appropriate
treatment

Ice-making system is

Run unit through

dirty

automatic clean cycle.
See CARE AND
CLEANING

Unit produces

Low water level

Check to see that

shallow or

overflow tube is fully

incomplete cubes,

seated

or the ice fill
pattern on the

Hot incoming water

Connect the unit to a

evaporator is

cold water supply.

incomplete

See INSTALLATION

Ice thickness

Adjust ice thickness.

adjustment dial

See ADJUSTING ICE

improperly set

THICKNESS

Incorrect incoming

Water pressure must

water pressure

be 20-120 psi

Unit is not level

See LEVELING THE
UNIT

29