Unvented natural gas log heater vanguard flame-max, Installation, Continued – Vanguard Managed Solutions FLAME-MAX User Manual

Page 10

Advertising
background image

UNVENTED NATURAL GAS LOG HEATER

VANGUARD FLAME-MAX

®

10

105187

Installation Items Needed

• hardware package (provided with heater)

• approved flexible gas hose (not provided)

(if allowed by local codes)

• sealant (resistant to propane/LP gas, not

provided)

• electric drill with 3/16" drill bit (metal

or masonry as applicable)

• flathead screwdriver

1.

Apply pipe joint sealant lightly to male
threads of the fitting to be threaded into
gas regulator. Connect approved flex-
ible gas hose to gas regulator of heater
(see Figure 11, page 11).

IMPORTANT:

Hold gas regulator with

wrench when connecting flexible gas
hose.

2.

Locate two masonry screws in hard-
ware package.

3.

Place heater base in fireplace.

4.

Place logs in their proper position on
heater base.

5.

Center heater base and logs front-to-
back and side-to-side in fireplace.

6.

Carefully remove logs without moving
heater base.

7.

Mark screw locations through one hole
on each side of the mounting bracket
(see Figure 12, page 11). If installing
in a brick-bottom fireplace, mark screw
locations in mortar joint of bricks.

Area of Various Standard

Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

INSTALLING HEATER BASE
ASSEMBLY

WARNING: You must secure

this heater to fireplace floor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.

WARNING: If installing in a

sunken fireplace, special care is
needed. You must raise the fire-
place floor to allow access to
heater control panel. This will in-
sure adequate air flow and guard
against sooting. Raise fireplace
floor with noncombustible mate-
rial. Make sure material is secure.

CAUTION: Do not pick up

heater base assembly by the
burner. This could damage
heater. Only handle base assem-
bly by grates.

INSTALLATION

Continued

INSTALLING DAMPER
CLAMP ACCESSORY FOR
VENTED OPERATION

Note:

When used as a vented heater, appli-

ance must be installed only in a solid-fuel
burning fireplace with a working flue and
constructed of non combustible material.

If your heater is a manually controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode:

1.

The fireplace does not meet the clear-
ance to combustibles requirements for
vent-free operation

2.

State or local codes do not permit vent-
free operation

3.

You prefer vented operation

If reasons number 1 or 2 above apply to you,
you must permanently open chimney flue
damper. You must install the damper clamp
accessory (to order, see Accessories, page
29). This will insure vented operation (see
Figure 10). The damper clamp will keep
damper open. Installation instructions are
included with clamp accessory.

See chart below for minimum permanent
flue opening you must provide. Attach
damper clamp so the minimum permanent
flue opening will be maintained at all times.

Chimney

Minimum Permanent

Height (ft.) Flue Opening (sq. ins.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

CAUTION: Do not remove the

metal data plates attached to the
heater base assembly. The data
plates contain important warranty
information.

IMPORTANT:

Make sure the heater burner

is level. If heater is not level, heater will not
work properly.

Figure 10 - Attaching Damper Clamp

Damper
Clamp

Masonry Fireplace

Manufactured Fireplace

Damper

Damper
Clamp

Damper

Advertising