Vinotemp WINEMATE VINO-1900SS User Manual

Page 3

Advertising
background image

- 2 -

• There is a gravity drain line and the unit shall be installed level or with a

slight angle toward the drain connection. If rise-up is needed, a
condensation pump must be used.

4. Refrigeration Piping, Evacuating, Charging and Starting

CAUTION:

ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE

READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED
CHARGES ARE FOR REFERENCE ONLY.

CHARGE 15% MORE REFRIGERANT IN THE SUMMER IF THE UNIT IS

EQUIPPED WITH A LOW AMBIENT CONDITION KIT.

• The installation order starts from condensing unit (including the receiver,

discharge valve), liquid line filter-drier, moisture-liquid indicator/sight glass,
liquid line, to evaporator unit (including liquid line connection, solenoid
valve, expansion valve, and suction line connection), returning to insulated
suction line, suction valve and then condensing unit.

• Use inverted siphons to prevent liquid from flooding back to the

compressor and aid oil returning to the compressor.

• Charge the system after pipe brazing, leak testing and evacuating.
• The subcooling at the condensing unit shall be around 10

°

F. The charge

may be complete when there are no more bubbles forming in the sight
glass.

• The evaporator superheat is set around 8-10

°

F at factory.

• The temperature split crossing the evaporator shall be 8-10

°

F at 55

°

F

wine room temperature.

• Suction pressure: 30-35 psig
• Head pressure: 125-150 psig at 70 -90

°

F ambient temperatures.


The line sizes and refrigerant charges are listed as follows.

MODEL

REFRIGERATION

LINES

LIQUID

LINE

SUCTION

LINE

DRAIN

LINE

CHARGE

VINO-1500SS

<= 50 FT

1/4"

OD

3/8” OD

1/2” OD

R134a/

15 OZ

VINO-1900SS <=50

FT

1/4"

OD

3/8” OD

3/8” OD

R134a/

15 OZ


NOTES:
THE VALVE CONNECTION SIZES OF CONDENSING UNIT AND THE LINE

CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY
THE SAME AS THE ABOVE SPECIFIED LINE SIZES.

IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORATOR

UNIT, USE THE SUCTION LINE ONE LISTED SIZE SMALLER.