Unvented natural gas log heater vanguard flame max, Installation – Vanguard Heating UNVENTED (VENT-FREE) NATURAL GAS LOG HEATER User Manual

Page 12

Advertising
background image

12

105273

UNVENTED NATURAL GAS LOG HEATER

VANGUARD FLAME MAX

®

INSTALLATION

Continued

CONNECTING TO GAS
SUPPLY

NOTICE: A qualified service per-
son must connect heater to gas
supply. Follow all local codes.

Installation Items Needed

Before installing heater, make sure you have
the items listed below.

• piping (check local codes)

• sealant (resistant to LP gas)

• manual shutoff valve *

• test gauge connection *

• sediment trap

• tee joint

• pipe wrench

* An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the optional A.G.A. design-certified
manual shutoff valve from your dealer. See
Accessories, page 25.

CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

WARNING: Never connect

heater to private (non-utility) gas
wells. This gas is commonly
known as wellhead gas.

CAUTION: Avoid damage to

control. Hold gas fitting with
wrench when connecting it to gas
piping and/or fittings.

Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 13).

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Figure 13 - Gas Connection

* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 25.

** Minimum inlet pressure for purpose of input adjustment.

3" Minimum

Gas Control

From Gas Meter (5"
W.C.** to 10.5" W.C.
Pressure)

A.G.A. Design-Certified
Manual Shutoff Valve With
1/8" NPT Tap*

Approved Flexible Gas
Hose (if allowed by
local codes)

Tee Joint

Cap

Sediment
Trap

Pipe Nipple

Advertising