Fresh air for combustion and ventilation – Vanguard Managed Solutions VP1000B User Manual

Page 8

Advertising
background image

8

099406

FRESH AIR

FOR

COMBUSTION

AND

VENTILATION

Continued

VENTILATION AIR

(Continued)

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3,
Air for Combustion and Ventilation
for required size of ventilation grills or ducts.

IMPORTANT:

Do not provide openings for inlet or outlet air into attic if attic has a

thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic

Outlet
Air

Inlet
Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic