Vinotemp WINE-MATE VINO-4500SSL User Manual

Page 18

Advertising
background image

- 17 -

Fig. 7 Liquid Filter Fig. 8 Liquid Indicator

Fig. 9 Temperature Controller (4.25”L X 3.75D X 4.25”H)

2. Evaporator Unit Installation

1) The WM-15~65SFCL evaporator units shall be installed for ceiling mount with

the supply air toward horizontal and return air on the bottom.

2) Air supply shall be unobstructed minimum 12” for a direct blow installation;

leave 2” clearance for a deflector installation; air return shall be unobstructed
minimum 6”.

3) The units may be recessed into the ceiling with short curved rectangular ducts;

CFM must be checked.

4) There is a gravity drain system used, so the unit shall be installed level or with

a slight slope downward the drain connection and the drain line shall be
installed slope down toward the drain. If rise-up is needed, a condensation
pump must be used.

3. Condensing Unit Installation

CAUTION:
Low ambient condition kit is required if the installation area will be below
50

°

F.

If the condensing unit is equipped with a low ambient condition kit,

do not turn on the compressor until the condensing unit has been powered
for minimum 12 hours.