3. Quick Start

This Quick Start Guide describes a simplified installation procedure for the

IPS-800CE-D16 (8-Plugs) and the IPS-1600CE-D16 (16-Plugs) hardware,

which will allow you to communicate with the unit in order to demonstrate

basic features and check for proper operation.
Note that this Quick Start Guide does not provide a detailed description of

unit configuration, or discuss advanced operating features in detail. For more

information, please refer to the Installation, Configuration and Operation

sections in this User's Guide.

3.1. Hardware Installation

3.1.1.

Apply Power to the IPS

Refer to power rating nameplate on the IPS back panel, and then connect the

IPS unit to an appropriate power source. Both the IPS-800CE-D16 and the

IPS-1600CE-D16 should be connected to a 100 to 240 VAC power source.

Note that the IPS features two separate AC inputs; connect power cables to

the unit's Circuit "A" and Circuit "B" Power Inlets, install the cable keepers as

described in Section 4, then connect the cables to an appropriate power source.
Models IPS-800CE-D16 and IPS-1600CE-D16 will both support up to 16

Amps maximum per power circuit, for a total of 32 Amps.

Note:

Each individual output plug on the IPS unit will support up to

10 Amps maximum.

Set the Main Power Switch in the ON position; the ON LED should light, and

the RDY LED should begin to flash. This indicates that the IPS is ready to

receive commands.