SPECIFICATIONS

ELECTRICAL RATINGS [@ 77

°

F (25

°

C)]:

Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.455 amp

Relay Load Ratings:

Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay: 2.0 amp @ 120 VAC 50/60 Hz

(resistive)

Flame Current Requirements:

Minimum current to insure flame detection: 1

µ

a DC*

Maximum current for non-detection: 0.1

µ

a DC*

Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe
lead

OPERATING TEMPERATURE RANGE:

-40

°

to 175

°

F (-40

°

to 80

°

C)

HUMIDITY RANGE:

5% to 93% relative humidity (non-condensing)

MOUNTING:

Surface mount multipoise

Timing Specs: (@ 60 Hz)

maximum

Flame Establishing Time:

2 sec

Flame Failure Response Time:

2 sec

Gases Approved: Natural, Manufactured, Mixed, Liquid
Petroleum, and LP Gas Air Mixtures are all approved for
use.

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise)

PRE-PURGE

TRIAL FOR IGNITION
PERIOD

IGNITION ACTIVATION
PERIOD

RETRIES

VALVE SEQUENCE
PERIOD

INTERPURGE

POST-PURGE

LOCKOUT TIME

HEAT DELAY-TO-FAN-ON

HEAT DELAY-TO-FAN-OFF*

COOL DELAY-TO-FAN-ON

COOL DELAY-TO-FAN-OFF

IGNITOR WARM-UP

HUMIDIFIER

ELECTRONIC AIR
CLEANER

15

4

4

4 times

12

15

5

122

45

60/90/

120/180

0

0

20

YES

YES

50A62-820

* This time will vary depending on option

switch position. The control is factory-set
at 60 sec. heat delay-to-fan-off. See
OPERATION section for further
information.