Watlow Electric Gateway & DeviceNet User Manual

Rui/gateway & devicenet, Configuring the rui/gateway on devicenet, Using rsnetworx

Advertising
background image

RUI/Gateway & DeviceNet

TM

Configuration & Ladder Logic Example

Using an Allen-Bradley CompactLogix PLC

Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2007 Watlow Electric Mfg Co 1

4/08

Configuring the RUI/Gateway on DeviceNet

TM

Using RSNetWorx


1.

Prior to making the physical connections on the network setup the gateway DeviceNet

TM

communications parameters per your network requirements, i.e., baud rate and node

address. If your not sure how to do this go to

http://www.watlow.com

and download the EZ-

ZONE

®

PM Communications Manual and follow the procedure defined in the DeviceNet

TM

chapter.

2.

Once the gateway communications parameters for DeviceNet

TM

are set according to your

network requirements connect the gateway into the network and do the following:

a. Run RSLinx software and configure the driver of choice

b. Run RSNetWorx software.

3.

As shown below (within RSNetWorx software), click on the online command from the tools
toolbar and then select the appropriate communications path to browse the DeviceNet

TM

network. Set up in previous step using RSLinx software.


















4.

After successfully browsing the network all nodes on the network will appear in the graphical

Advertising