RUI/Gateway & DeviceNet

TM

Configuration & Ladder Logic Example

Using an Allen-Bradley CompactLogix PLC

Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2007 Watlow Electric Mfg Co 13

4/08

Reading and Writing to/from RUI/Gateway Using RSLogix 5000

24. The rung of logic below when enabled, will execute an explicit message sent to the gateway

where it will then be routed out over Standard Bus to the EZ-ZONE

®

PM control defined by

the instance (

oSt prompt). Because the CIP offset is set to 12 for gateway instance 4 this

message will be routed to PM4. When done, the destination tag identified under the

configuration tab “EEPROM _Status” (see below) will contain the value of either 106 being

enabled or 59 being disabled.