BMC and BMC-6X Installation and Operation Manual

SENSOR FAULT

All Off, All On

Default: All On

Button: MENU/<System Startup>/..../Sensor Fault
The Sensor Fault will determine the operating status of all output stages that are set to Auto
when a sensor reads Short or Open.

BACK

SAVE

--------- SENSOR FAULT --------

All Off

All On

RESET MODE

When All-On is selected, the BMC will turn all boilers On to a 100% when System reads Short or Open and Outdoor is below
Outdoor Cutoff. When Outdoor reads Short or Open, the BMC will turn all boilers On to a 100%.

When All-Off is selected, the BMC will turn all boilers Off when either System or Outdoor sensor reads Short or Open.

SET POINT MODE

When All-On is selected, the BMC will turn all boilers On to a 100% when the System sensor reads Short or Open.

When All-Off is selected, the BMC will turn all boilers Off when the System sensor reads Short or Open.

The Outdoor Sensor Short or Open status will not affect the control operation in Set Point mode.

SETTING THE CONTROL TO FACTORY DEFAULTS

To Reset the BMC control to its original factory defaults, power down the control. Hold
down the two right most buttons while powering the control back up until the

Total

Clear Started screen appears. The Display will direct you to the Startup menu to
program the control after the defaults are loaded.

TOTAL CLEAR STARTED

Release buttons

and

Please Wait

NOTE: When resetting the control to original factory defaults all control settings will be overwritten and will no longer exist.

ALERT

Do not turn off power to control until all Startup settings have been made. Otherwise, the next
power-up will be set to many Startup factory settings that might not fit your application.