Checkout procedure, Universal control systems — control supplement, Room thermostat anticipator settings – Weil-McLain Boiler User Manual

Page 21

Advertising
background image

1

Part Number 550-110-646/0607

Universal control systems — Control supplement

1. See pages – for “Operating instructions.”
. Raise room thermostat to call for heat. Damper actuator will slowly open damper.
. When damper is fully open, main gas valve will open and main burners will ignite.

Damper must be fully open before main burners light. If damper does not fully

open, flue products will escape into house, causing severe personal injury or

death.

. Lower thermostat setting. Main burner flames will go out, then damper will close.
. Repeat steps 1 through  several times to verify operation.
. Return thermostat to normal setting.

Room thermostat anticipator settings

Water without tankless heater — 0.40 amps

Water with tankless heater — 0.20 amps

Steam — Select based on gas valve and damper. See table below.

Checkout procedure

Boilers with
United Technologies
Ignition control

(control load of 0.10 amps is
included in the values at right)

Gas valve

Without

damper

(amps)

With

Effikal

damper

(amps)

With

Johnson

damper

(amps)

Honeywell VR8200

0.60

0.70

0.80

Honeywell VR8300

0.80

0.90

1.00

Robertshaw 7200ER

0.50

0.60

0.70

Robertshaw 7000ERHC

0.80

0.90

1.00

White-Rodgers 36E

0.40

0.50

0.60

White-Rodgers 36C

0.70

0.80

0.90

Boilers with
Honeywell
Ignition control

(control load of 0.20 amps is
included in the values at right)

Gas valve

Without

damper

(amps)

With

Effikal

damper

(amps)

With

Johnson

damper

(amps)

Honeywell VR8200

0.70

0.80

0.90

Honeywell VR8300

0.90

1.00

1.10

Robertshaw 7200ER

0.60

0.70

0.80

Robertshaw 7000ERHC

0.90

1.00

1.10

White-Rodgers 36E

0.50

0.60

0.70

White-Rodgers 36C

0.80

0.90

1.00