Thermostat, Fan control – White Rodgers G1N 4R9 User Manual

Page 11

Advertising
background image

OUTSIDE VIEW OF THE ELECTRIC ELEMENT


THERMOSTAT


The thermostat must be installed on an inside wall in a location where it is not likely to be affected by the draft
coming from an air outlet. It must be installed at a minimum of 55 inches above the floor.

N.B. The combined wood / electric model must be installed with two thermostats at same level.


FAN CONTROL

The fan control setting varies depending on the type of heating installation. The setting “out of service” is preset at
110

o

F in factory. This setting should provide a proper operation for most installations. The temperature “in service” is

pre-set at 150

o

F.


It is preferable for a prolonged operation of the blower that the setting “out of service” be low enough. But a setting
“out of service” too low will cause a cold air circulation. To modify the setting, turn the button at the desired position on
the temperature scale.

The adjustment of all controls must be performed by a qualified technician. The controls setting and the blower
speed must conform to the recommendations of the “Warm Air Heating and Air Conditioning National Association”. To
obtain a continuous air circulation during summer, push the manual switch of the limit control from the “automatic”
position to the “manual or summer” position.

The switch located below the limit control or on the electric unit, controls the low speed either at the “on” position or
the “off” position. For a better efficiency we recommend to leave the high speed on automatic(wood side fan limit
control).

11

Advertising