Line Filtering Configurations For Controls

Figure

3 -

These three diagrams show you filter configurations for removing input power

noise. Choose the one best suited for your system. For very dirty or critical
applications - use

a

microcomputer-regulated power supply or Uninterruptable

Power Supply (U.P.S.) Don’t fasten common mode line filters or filters with

metal cases to metal that is at ground potential. This prevents ground loops
and maintains filter effectiveness.

Differential Mode
Filter

Wiring

Ll D.M. Line Filter

.

NOTE: Keep filters
12 inches or less

from the control.

Minimize

the line

distance where

nolse can be re-
introduced to

control.

Control

Common Mode Filter

Wiring

2

NOTE: To prevent
ground loops do not

fasten

common

mode line filters or

filters with metal
cases to metal that

is at ground poten-

tlal. Doing so will

reduce filter effec-

tiveness.

Figure 5 -

Combination

Differential/

Common Mode Filter

Wiring

C.M.

Line

Filter

Control

I

Ground

Control

10 WATLOW Series 980/985 User's Manual

Install and Wire, Chapter 2