Start-up, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 61

Advertising
background image

Part number 550-142-054/0411

61

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Start-up

(continued)

3. Inject all of the inhibitor supplied with the boiler. Allow time for

the water to circulate and mix. Then check the inhibitor level. Add

additional inhibitor if necessary.

Check/verify water chemistry

1. The system may have residual substances that could affect water

chemistry.

2. After the system has been filled and leak tested, verify water pH

and chlorine concentrations are acceptable.

3. Verify antifreeze concentration, when used.
4. Follow the instructions on the Sentinel test kit to sample the system

water and verify inhibitor concentration.

Check inhibitor concentration annually

1. Test the pH of a sample of system water at least annually. The pH

of the water mixture must be between 7.0 and 8.5. (Or use the

Sentinel inhibitor test kit to check concentration.)

2. If pH is outside this range (or inhibitor test kit indicates low level),

the inhibitor level may not be sufficient to prevent corrosion.

3. Test antifreeze concentration.

Test antifreeze concentration at least annually. If concen-

tration is low, add antifreeze or drain system and refill

with correct mixture.

4. Follow instructions on antifreeze container to determine the

amount of antifreeze needed.

DO NOT

exceed 50% by volume

concentration of antifreeze.

5. Check inhibitor level after adjustments are made.

Verify gas/air orifice plate

The proper orifice plate must be used

. Failure to do

so will cause severe personal injury, death or substantial

property damage.

1. Remove the jacket front panel.
2. Read the boiler size written on the gas/air orifice label tab, verifying

the correct size. See Figure 5, page 8 for details.

3. The orifice plate must be plain aluminum for natural gas. For

propane gas, the exposed tab of the plate should be red.

4. Replace the orifice plate if necessary, following the guidelines on

page 8.

Check thermostat circuit(s)

1. Disconnect the two external wires connected to the boiler thermo-

stat terminals (see Field wiring, beginning on page 56 for terminal

locations).

2. Connect a voltmeter across these two incoming wires. Close each

thermostat, zone valve and relay in the external circuit one at a

time and check the voltmeter reading across the incoming wires.

3. There should NEVER be a voltage reading.
4. If a voltage does occur under any condition, check and correct the

external wiring. (This is a common problem when using 3-wire

zone valves.)

5. Once the external thermostat circuit wiring is checked

and corrected if necessary, reconnect the external ther-

mostat circuit wires. Allow the boiler to cycle.

Inspect/fill condensate system

Inspect/check condensate lines and fittings

1. Inspect the condensate drain line, condensate PVC fit-

tings and condensate trap.

Fill condensate trap with water

1. Loosen the hose clamp (Figure 70, item 2) that secures

the condensate trap (Figure 70, item 1) to the bottom

of the recuperator (Figure 70, item 3).

2. Pull the condensate trap tube off of the recuperator

condensate drain nipple.

3. Use a funnel to feed water into the top of the conden-

sate tube.

4. Continue filling until water begins to flow out through

the condensate line (Figure 70, item 4).

5. Re-attach the condensate trap to the bottom of the

recuperator. Secure with the hose clamp.

6. Check for any leaks in the condensate drain line or fit-

tings. Repair any leaks.

7. Remove the temporary clamp (see step 2, above) from

the condensate drain tube.

The condensate trap must be filled with water

during all times of boiler operation to avoid

flue gas emission from the condensate drain

line. Prime the condensate trap by pouring

water into the outlet tee while restricting flow

in drain tube if boiler has been out of service

for an extended period. Failure to fill the trap

could result in severe personal injury or death.

Figure 70

Condensate trap assembly

Advertising