Install system water piping – Weil-McLain Ultra Electric Water Heater User Manual

Page 4

Advertising
background image

Part number IWHA016A/1103

4

PLUS Line Instruction Manual Supplement

PLUS &

PLUS

WATER

HEATERS

WITH

GAS

-

FIRED

WATER

BOILERS

Install system water piping

(space heating)

(continued)

1

Figure 2

Zone valve zoning plus optional
water heater piping

Zoning with zone valves

1. Connect boiler to system as shown in Figure 2

when zone valve zoning. The primary/secondary
piping shown ensures the boiler loop will have
sufficient flow. It also avoids applying the high head
of the boiler circulator to the zone valves.

2. When using a closed-type expansion tank, connect

the expansion tank and make-up water piping as
shown in Figure 1, page 3.

3. Connect water heater (domestic hot water) piping

to indirect storage water heater as shown.

The

PhD Control Module turns off

space heating during water heater heating.
The boiler circulator will turn off,
preventing hot water from circulating to
the system. The flow/check valve shown
on the boiler outlet piping prevents
gravity circulation in the boiler loop
during water heater heating.

4. Controlling the system circulator

a. To cycle the system circulator from the Ultra PhD

control module, add a circulator relay wired to the
boiler circulator terminals as shown on page 8.

Legend

Figure 2

1

Ultra boiler

2

Indirect water heater (water heater), if used

3

Boiler relief valve (see boiler manual for piping details)

4

Relief valve discharge piping (see boiler manual for details)

5

Water heater circulator (see page 7 for suggested sizing)

6

Isolation valves

7

System circulator

8

Diaphragm (or bladder) type expansion tank (see page 3
for piping of closed-type expansion tank, if used)

9

Air separator [with automatic air vent only on systems using
diaphragm (or bladder) type expansion tank]

10 Flow/check valves (with weighted seats to prevent gravity

circulation)

11 Purge/drain valves

12 Boiler circulator

13 Zone valves, typical

20 Make-up water supply

21 Primary/secondary connection

NOTE 1:

To ensure adequate flow rate through the
boiler, use the following pipe size on all boiler
loop piping (connecting boiler to and from
the primary/secondary connection, item 21):
Ultra-80 or Ultra-105 – 1" or larger.
Ultra-155 or Ultra-230 – 1¼" or larger.
Ultra-310 – 1½" or larger.

Use at least the minimum piping size above
and pipe the boiler using only primary/
secondary piping as shown. Failure to
follow these guidelines could result in
system problems.