INSTALLATION

LOCATING YOUR BUILT-IN SIDE BURNER APPLIANCE

When determining a suitable location for your Built-In Side Burner installation, give
attention to concerns such as exposure to wind, proximity to traffic paths, and keeping
any gas supply lines as short as possible. Never locate the Summit

®

Built-In Side Burner

in a garage, breezeway, shed, under overhang, or other enclosed area. Locate the Side
Burner and structure so there is enough room to safely evacuate the area in case of a
fire.

CLEARANCE FROM COMBUSTIBLE SURFACES OR STRUCTURES

ƽ WARNING: Clearance from the outside walls of the sides

and back of the Built-In Side Burner must be a minimum
of 24 inches (61 cm) from any combustible surface. Refer
to “Installation/Gas Instructions” section before starting
installation.

C

A

B

BUILT-IN STRUCTURE CUTOUT DIMENSIONS

All dimensions are to finished surfaces.

ƽ WARNING: All counter top finished surfaces must be

constructed of a noncombustible material.

SIDE BURNER

Cut out Dimensions

Tolerances

A

12 3/8" (31.4 cm)

+ 1/8" - 1/8" (3.18mm)

B

7 7/8" (20 cm)

-

C

27" (68.6 cm)

+ 1/8" - 1/8" (3.18mm)

C

A

A

B

B

B

1

SIDE BURNER LOCATION

A

Any Surface

B

24" (61 cm) From Any Combustible Surface

C

Side Burner

1

Note: For a countertop treatment: Recommended 3/4" (19 mm) overhang.
Notch front edge for frame to fully slide in.

ƽ DANGER

The structure, “island” counter tops and adjacent work areas
for the Built-In Side Burner installation must be built from
noncombustible materials only. Incorrect installation may
result in a fire, which can cause serious bodily injury or
death, and cause damage to property.

NOTE: If you have questions on what materials are considered noncombustible, contact
you local building supplier or fire department.