Ac output wiring - zone 2, Dc output wiring - zone 2, Output 2 wiring – Watlow Series 733 Service User Manual

Page 9

Advertising
background image

9

WATLOW Series 733/734 Service Manual

Install & Wire, Chapter 1

Output 2 Wiring

Figure 16 -
DC Output 2 Wiring.

Figure 15 -
AC Output 2 Wiring.

1

2

3

4

5

6

7

8

9

10

11

12

External

Load

+

-

-

+

1

2

3

4

5

6

7

8

9

10

11

12

External

Load

COM

L1

L2

Fuse

NO

AC Output Wiring - Zone 2

Solid State Relay

with

Mechanical Relay

with

Contact Suppression

Contact Suppression

Form A, 0.4 Amps

Form A, 1 Amp

Off state impedance: 20K max.

Off state impedance: 20K min.

73XX-XXBX-XXXX

73XX-XXDX-XXXX

Solid State Relay

without

Contact Suppression

Form A, 04 Amps
Off state impedance: 31M max.
73XX-XXKX-XXXX

DC Output Wiring - Zone 2

Switched DC
(Open Collector)

4-20mA Process Output

Non-isolated

Non-isolated

Minimum load resistance: 500

Load impedance: 600 max.

73XX-XXCX-XXXX

73XX-XXFX-XXXX

0-5V

О

О

О

О

О

(VDC) Process Output

Non-isolated
Load impedance: 10K min.
73XX-XXHX-XXXX

Advertising
This manual is related to the following products: