All direct-drive units with 460 and 575 voltage are shipped with

the wire labeled #116 connected to the “HIGH” speed tap on

the blower motor. If the medium speed is required, connect wire

#116 to the “MED” speed tap and the blue motor lead to the

“HIGH” speed tap. If the low speed is required, connect wire

#116 to the “LOW” speed tap, the blue motor lead to the “HIGH”

speed tap and the orange motor lead to the “MED” speed tap.

COMPRESSORS

On some units the compressor is mounted on springs which

have been tightened down for shipment only.
After this unit is installed, back out the compressor bolts until

the sleeve clears the top grommet.

CAUTION: Do Not loosen compressor mounting bolts.

OPTIONAL ECONOMIZER RAIN HOOD

The following procedure should be used when assembling an

economizer rain hood onto a unit. Refer to Figure 3. The

outdoor and return air dampers, damper actuator, the linkage

and all the controls are factory mounted as part of the

economizer option.

All of the hood components, including the filters, the gasketing

and the hardware for assembling are located above the top

filter racks within the filter section. The outdoor air sensor is in

the bag of parts located at the bottom of the return air section.

1. With filter section access panel removed, take out hood

components, filters and sensor described above. Remove

and discard outdoor air opening cover on back unit (Upper

right hand corner).

2. Remove the 1/2" knockout (A) in the units rear panel (lo-

cated to the right side of the outdoor air opening). Insert the

two loose wires from inside the unit, into the 1/2" bushing

provided. Insert wires and bushing into knockout. Snap

bushing into place.

3. Mount the outdoor air sensor to the rear panel, just below

the knockout described in Step 2. Secure with two

self-drilling screws at dimples (B) provided in the panel.

NOTE: Sensor must be positioned so that the sensing

ports are at the top (louvers pointing downward)

and terminal connections to the right.

4. Connect the two wires, indicated in Step 2, to the sensor as

follows:

Wire #73 to terminal (+)

Wire #74 to terminal (S)

5. Assemble the LH and RH side plates to the top cover

(2 screws each side) to form the hood. Apply gasketing to

the flange surface on each side plate. Extend gasketing

1/4" beyond top and bottom of each flange to insure ade-

quate corner sealing. Secure this assembly to the unit back

panel (upper right hand corner). First, remove screw (C) on

unit top cover. Then slip flange of hood cover in under

flange of unit top cover, replace screw (C), engaging hole

(E) in hood flange and tighten. Attach the two side plates to

the unit panel by using two self-drilling screws for each side

plate at dimples (D) provided in the panel.

6. Position fillpiece at bottom of hood, between the two side

plates but do not secure at this time. (Slotted openings

MUST be downward for drainage). After fillpiece is properly

positioned, note where contact is made with the unit panel.

Remove fillpiece and apply gasket material to this area to

provide a seal. Reposition fillpiece and secure with 2

screws.

7. Install the two filters into the hood assembly, sliding down

along retainers on side plates, into fillpiece at bottom of

hood.

NOTE: Install filters so that “Air Flow” arrows point toward

the unit.

8. Install filter cover over the end of the hood with one screw

(center of hood), securing filters into position.

CAUTION: When proceeding with steps 9 and 10, extreme

care must be exercised while turning both the set

point and minimum position adjusting screws to

prevent twisting them off.

9. The enthalpy set point for the dampers may now be set by

selecting the desired set-point from graph in Figure 6. For a

single enthalpy economizer, carefully turn the set-point

adjusting screw to the “A”, “B”, “C” or “D” setting

corresponding to the lettered curve. For a dual enthalpy

economizer, carefully turn the set-point adjusting screw

fully clockwise past the “D” setting.

035-12046-003-A-0204

Unitary Products Group

5

FIG. 3 - ECONOMIZER RAIN HOOD ASSEMBLY (OPTION)

B

GASKET

C

HOOD
COVER

OUTDOOR AIR
SENSOR

A

FILTER SECTION
ACCESS PANEL

D

GASKETED
FLANGE

R. H.
SIDE
PLATE

D

E

D

D

GASKETED
FLANGE

FILTER
COVER

L. H. SIDE
PLATE

FILTERS

FILLPIECE

OUTDOOR AIR
OPENING COVER

SIDE DUCT

APPLICATION SHOWN