York YCJF24 User Manual

Page 30

Advertising
background image

Subject to change without notice. Printed in U.S.A.

413437-YTG-C-0908

Copyright © 2008 by Johnson Controls, Inc. All rights reserved.

Supersedes: 413437-YTG-B-0608

Johnson Controls Unitary Products

5005 York Drive

Norman, OK 73069

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

YCJF60S41S1

INDOOR COIL MODEL NO.

FC/MC/PC62

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1400

1600

1800

ID

DB

(°F)

80 80

75

80

80

80 80 75

80

80 80 80

75 80 80

ID

WB

(°F)

57 62 62 67 72 57 62 62 67 72 57 62 62 67 72

65

T.C.

54.5 57.8 56.7 62.8 68.7 55.3 59.1 58.5 64.7 69.7 56.1 60.4 60.2 66.6 70.7

S.C.

54.0 49.2 40.9 40.7 32.5 56.2 52.4 43.1 42.9 34.1 58.5 55.7 45.3 45.1 35.8

KW

2.7 2.7 2.6 2.7 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

75

T.C.

52.7 55.6 54.4 60.5 66.0 54.8 56.8 56.1 62.1 66.9 56.9 58.0 57.7 63.7 67.9

S.C.

52.3 48.1 39.9 39.8 31.5 54.3 51.1 42.2 41.9 33.1 56.4 54.2 44.4 44.1 34.7

KW

3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

85

T.C.

50.8 53.5 52.2 58.1 63.3 54.3 54.5 53.7 59.5 64.2 57.7 55.6 55.2 60.8 65.1

S.C.

50.6 47.1 38.9 38.9 30.5 52.4 49.9 41.2 41.0 32.1 54.3 52.7 43.6 43.0 33.6

KW

3.5 3.6 3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5

95

T.C.

49.0 51.4 50.0 55.8 60.5 53.7 52.3 51.3 56.8 61.4 58.4 53.2 52.6 57.9 62.3

S.C.

48.9 46.0 37.9 38.1 29.5 50.5 48.6 40.3 40.0 31.0 52.2 51.2 42.7 41.9 32.6

KW

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

105

T.C.

46.4 48.2 46.9 52.5 57.0 50.0 49.3 48.1 53.3 58.0 53.7 50.4 49.3 54.2 59.0

S.C.

46.5 44.6 36.7 36.5 28.1 48.0 47.0 39.0 38.5 29.6 49.5 49.3 41.2 40.5 31.1

KW

4.8 4.8 4.8 4.7 4.7 4.8 4.8 4.8 4.7 4.7 4.7 4.8 4.8 4.7 4.7

115

T.C.

43.8 45.2 43.9 49.3 53.6 46.5 46.4 45.0 50.0 54.7 49.1 47.6 46.1 50.7 55.9

S.C.

44.1 43.3 35.5 35.0 26.8 45.5 45.4 37.6 37.1 28.3 46.9 47.5 39.8 39.2 29.7

KW

5.6 5.6 5.7 5.4 5.4 5.5 5.5 5.6 5.4 5.3 5.5 5.5 5.5 5.4 5.3

125

T.C.

41.3 42.2 40.8 46.0 50.2 42.9 43.5 41.9 46.6 51.5 44.5 44.9 42.9 47.2 52.7

S.C.

41.8 41.9 34.3 33.5 25.5 43.1 43.8 36.3 35.7 26.9 44.4 45.6 38.3 37.8 28.3

KW

6.4 6.4 6.5 6.1 6.0 6.3 6.3 6.4 6.1 6.0 6.2 6.2 6.3 6.1 6.0

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

FC/MC/PC60

0.96 0.98 1.00

HC60

0.96 0.98 1.00

AV/SV60

0.97 0.99 0.97

MV20D

FC/MC60D

0.97 0.99 0.98

MA20D

FC/MC62D

1.00 1.00 1.00

MV20D

FC/MC62D

1.01 1.01 0.98

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

P(C,V)9*D20

HC60D

0.95 0.93 0.97

PV8*C20

HD60

0.99 0.99 0.99

P(C,V)9*C20

HD60

0.99 0.99 0.98

P(C,V)9*D20

HD60

0.98 0.97 0.97

PV8*C20

FC/MC62D

1.00 1.00 0.99

P(C,V)9*C20

FC/MC62D

0.98 0.97 0.98

P(C,V)9*D20

FC/MC62D

0.99 0.96 0.97

Y*(8,L)C*C20

FC/MC62D

0.99 0.97 0.95

Y*9C*C20

FC/MC62D

0.98 0.96 0.98

Y*9C*D20

FC/MC62D

0.99 0.97 0.97

Y*9C*D20

HC60

0.96 0.92 0.97

Y*(8,L)C*C20

HD60

0.99 0.98 0.96

Y*9C*C20

HD60

1.00 0.98 0.98

Y*9C*D20

HD60

0.99 0.96 0.98

G*9V*C20

FC/MC62D

0.98 0.96 0.98

G*9V*D20

FC/MC62D

0.99 0.97 0.97

G*9V*D20

HC60

0.96 0.92 0.97

G*9V*C20

HD60

1.00 0.98 0.98

G*9V*D20

HD60

0.99 0.96 0.98

Advertising