Configuration

4–14

445-0089-01-01

Bulk Charge Mode
Settings

•

Max Voltage
This is the maximum available charging voltage for the Bulk charging stage.

•

Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Bulk charging stage.

•

Threshold Voltage and Timeout
When the battery voltage goes above this value for the Threshold Timeout
specified, the unit goes into Absorption charging stage.

Absorption Mode
Settings

•

Max Voltage
This is the maximum charging voltage for the Absorption charging stage.
Typically, the battery will be at this voltage for the duration of this stage.

•

Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Absorption charging stage.

•

Max Timeout
This is the maximum amount of time that the unit will stay in the Absorption
stage.

•

Threshold Current (%C) and Timeout
When battery current goes below this value (A as % of battery capacity in Ah)
for the Threshold Timeout, the unit goes into the next charging stage.

Overcharge Mode
Settings

•

Max Voltage
This is the maximum charging voltage for the Overcharge charging stage.
Typically the battery will be at this voltage for the duration of this stage.

•

Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Overcharge charging stage.

•

Max Timeout
The amount of time that the Overcharge stage will run.

Float Mode Settings

•

Max Voltage
This is the maximum available charging voltage for the Float charging stage.
Typically the battery will be at this voltage for the duration of this stage.

•

Max Current (%C)
The maximum available charging current (in A) as a percentage of battery
capacity (in Ah) for the Float charging stage.

•

Max Timeout
This is the maximum amount of time that the charger will be in Float stage.

•

Threshold Voltage and Timeout
When the battery voltage goes below this value for the Threshold Timeout
specified, the unit goes into Bulk charging mode.