PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet

of interconnecting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

Additional R-410A Charge / TXV Size for Various Matched Systems

Outdoor Unit

YZB1811

YZB02411

YZB03011

YZB03611

YZB04211

YZB04811

YZB06012

Required TXV

1

1TVM(901/4E1) 1TVM(902/4F1) 1TVM(903/4G1) 1TVM(904/4H1) 1TVM(904/4H1) 1TVM(905/4J1) 1TVM(906/4K1)

Factory Charge, lbs-oz

7-1

7-10

7-9

9-5

9-2

12-5

16-8

Indoor Coil

2

TXV Kit

3

- Additional Charge, Oz

Shaded areas indicate matches that require variable speed indoor unit to meet minimum efficiently standards.
Data provided for charge adder information only.

FC/MC/PC/UC18A

901 + 0

FC/MC/PC/UC18B

901 + 0

FC/MC/PC/UC24A

902 + 5

FC/MC/PC/UC24B

902 + 5

FC/MC/PC/UC30A

902 + 5

FC/MC/PC/UC30B

902 + 5

FC/MC/PC/UC36A

903 + 5

904 + 3

FC/MC/PC/UC36B

903 + 5

904 + 3

FC/MC/PC/UC36C

903 + 5

904 + 3

FC/MC/PC/UC48C

904 + 7

FC/MC/PC/UC48D

904 + 7

FC/PC/UC60C

905 + 12

FC/MC/PC/UC60D

905 + 12

MC61D

905 + 16

FC/MC62D

906 + 0

HC18A

901 + 0

HC30A

902 + 7

903 + 5

HC36B

904 + 5

HC42C

904 + 5

HC60D

905 + 10

HD24A

901 + 9

902 + 7

HD36B

903 + 9

904 + 10

HD48C

904 + 5

HD60D

905 + 10

AHP18B

901 + 0

AHP24B

902 + 6

AHP30B

903 + 9

AHP36C

903 + 14

904 + 13

AHP42C

904 + 13

AHP/SHP48D

904 + 7

905 + 8

AHP/SHP60D

905 + 8

AV24B

901 + 3

902 + 6

AV36C

903 + 14

904 + 13

AV/SV48D

904 + 20

904 + 10

905 + 8

F*FP024H06T2A

901 + 0

F*FP024H06T2B

901 + 0

F*FP030H06T2A

902 + 3

F*FP036H06T2A

903 + 7

904 + 5

F*FP042H06T2A

904 + 7

FOOTNOTES:

1. If indoor coil comes with a factory-installed TXV, it must be removed and replaced with the required TXV.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
3. A TXV kit must be used with these coils to obtain system performance (901, 902, 903, 904, 905 indicates 1TVM …series).