TABLE 5: COOLING CAPACITY DH078 (6-1/2 TON) UNIT
Air On
Evap. Coil
Temperature of Air on Condenser Coil 75°F
Temperature of Air on Condenser Coil 85°F
CFM
WB
(°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Tot.
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
1950
72 88.9
4.8
51.3
45.8
40.2
34.6
29.1
-
-
84.6
5.3
49.4
43.9
38.3
32.7
27.2
-
-
67 85.5
4.8
65.4
59.9
54.3
48.7
43.2
37.6
32.1
79.8
5.2
62.9
57.4
51.8
46.2
40.7
35.1
29.6
62 80.0
4.7
80.0
73.8
68.2
62.7
57.1
51.5
46.0
74.2
5.1
74.2
69.8
64.3
58.7
53.1
47.6
42.0
57 78.2
4.7
78.2
76.8
71.3
65.7
60.2
54.6
49.0
73.1
5.1
73.1
71.6
66.0
60.5
54.9
49.4
43.8
2275
72 91.3
4.8
56.3
49.7
43.2
36.6
30.0
-
-
87.1
5.3
54.5
47.9
41.4
34.8
28.2
-
-
67 87.9
4.8
71.4
64.9
58.3
51.7
45.1
38.6
32.0
82.2
5.3
69.1
62.5
56.0
49.4
42.8
36.2
29.7
62 82.2
4.7
82.2
79.1
73.3
66.7
60.1
53.5
47.0
76.4
5.2
76.4
74.2
69.4
62.8
56.3
49.7
43.1
57 80.4
4.7
80.4
79.7
76.5
70.0
63.4
56.8
50.3
75.2
5.2
75.2
74.5
71.3
64.8
58.2
51.6
45.0
2600
72 93.8
4.8
61.3
53.7
46.1
38.5
30.9
-
-
89.6
5.4
59.6
52.0
44.4
36.9
29.3
-
-
67 90.2
4.8
77.4
69.9
62.3
54.7
47.1
39.5
31.9
84.5
5.3
75.3
67.7
60.1
52.5
44.9
37.4
29.8
62 84.4
4.8
84.4
84.4
78.3
70.7
63.1
55.5
47.9
78.6
5.2
78.6
78.6
74.6
67.0
59.4
51.8
44.2
57 82.6
4.7
82.6
82.6
81.8
74.2
66.6
59.1
51.5
77.4
5.2
77.4
77.4
76.6
69.0
61.5
53.9
46.3
2925
72 94.5
4.8
65.3
56.6
48.0
39.4
30.7
-
-
90.5
5.4
63.7
55.1
46.5
37.8
29.2
-
-
67 90.9
4.8
83.2
73.5
64.8
56.2
47.6
38.9
30.3
85.4
5.3
80.1
71.5
62.8
54.2
45.6
36.9
28.3
62 85.0
4.8
85.0
85.0
82.0
73.3
64.7
56.0
47.4
79.4
5.2
79.4
79.4
77.4
68.8
60.1
51.5
42.9
57 83.1
4.7
83.1
83.1
82.8
74.1
65.5
56.9
48.2
78.2
5.2
78.2
78.2
77.8
69.2
60.5
51.9
43.3
3250
72 95.1
4.9
69.3
59.6
49.9
40.2
30.5
-
-
91.4
5.4
67.8
58.2
48.5
38.8
29.1
-
-
67 91.5
4.8
88.9
77.1
67.4
57.7
48.0
38.3
28.6
86.3
5.3
84.9
75.2
65.6
55.9
46.2
36.5
26.8
62 85.6
4.8
85.6
85.6
85.6
75.9
66.3
56.6
46.9
80.2
5.2
80.2
80.2
80.2
70.6
60.9
51.2
41.5
57 83.7
4.7
83.7
83.7
83.7
74.0
64.4
54.7
45.0
79.0
5.2
79.0
79.0
79.0
69.3
59.6
49.9
40.2
Temperature of Air on Condenser Coil 95°F
Temperature of Air on Condenser Coil 105°F
1950
72 80.3
5.8
47.5
42.0
36.4
30.8
25.3
-
-
74.6
6.3
45.1
39.6
34.0
28.5
22.9
-
-
67 74.1
5.7
60.4
54.9
49.3
43.7
38.2
32.6
27.1
67.4
6.1
57.6
52.1
46.5
40.9
35.4
29.8
24.3
62 68.5
5.6
68.5
65.8
60.3
54.7
49.2
43.6
38.0
63.3
6.0
63.3
60.8
55.2
49.7
44.1
38.6
33.0
57 68.0
5.6
68.0
66.4
60.8
55.2
49.7
44.1
38.6
63.0
6.1
63.0
61.2
55.6
50.1
44.5
39.0
33.4
2275
72 82.8
5.8
52.7
46.2
39.6
33.0
26.4
-
-
76.8
6.3
50.2
43.7
37.1
30.5
23.9
-
-
67 76.5
5.7
66.8
60.2
53.6
47.0
40.5
33.9
27.3
69.4
6.2
63.0
57.3
50.7
44.1
37.6
31.0
24.4
62 70.7
5.6
70.7
69.4
65.6
59.0
52.4
45.8
39.3
65.2
6.1
65.2
63.9
60.2
53.7
47.1
40.5
33.9
57 70.1
5.6
70.1
69.3
66.1
59.6
53.0
46.4
39.8
64.8
6.1
64.8
63.9
60.7
54.1
47.5
40.9
34.4
2600
72 85.4
5.9
57.9
50.4
42.8
35.2
27.6
-
-
78.9
6.4
55.3
47.7
40.2
32.6
25.0
-
-
67 78.8
5.8
73.1
65.5
57.9
50.4
42.8
35.2
27.6
71.3
6.2
68.5
62.5
54.9
47.3
39.7
32.2
24.6
62 72.9
5.7
72.9
72.9
70.8
63.2
55.7
48.1
40.5
67.0
6.1
67.0
67.0
65.2
57.6
50.1
42.5
34.9
57 72.2
5.7
72.2
72.2
71.5
63.9
56.3
48.7
41.1
66.6
6.2
66.6
66.6
65.7
58.1
50.5
42.9
35.3
2925
72 86.5
5.9
62.2
53.6
44.9
36.3
27.6
-
-
80.0
6.4
59.6
50.9
42.3
33.7
25.0
-
-
67 79.9
5.8
77.0
69.5
60.8
52.2
43.6
34.9
26.3
72.3
6.3
70.8
66.0
57.8
49.2
40.6
31.9
23.3
62 73.9
5.7
73.9
73.9
72.8
64.2
55.6
46.9
38.3
67.9
6.2
67.9
67.9
67.0
58.4
49.7
41.1
32.5
57 73.2
5.7
73.2
73.2
72.8
64.2
55.6
46.9
38.3
67.5
6.2
67.5
67.5
67.0
58.4
49.7
41.1
32.5
3250
72 87.7
5.9
66.4
56.7
47.1
37.4
27.7
-
-
81.0
6.4
63.8
54.1
44.4
34.8
25.1
-
-
67 81.0
5.8
81.0
73.4
63.7
54.0
44.4
34.7
25.0
73.2
6.3
73.2
69.4
60.8
51.1
41.4
31.7
22.0
62 74.9
5.7
74.9
74.9
74.9
65.2
55.5
45.8
36.1
68.8
6.2
68.8
68.8
68.8
59.1
49.4
39.7
30.0
57 74.2
5.7
74.2
74.2
74.2
64.5
54.9
45.2
35.5
68.4
6.2
68.4
68.4
68.4
58.7
49.0
39.3
29.6
Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
1950
72 69.0
6.8
42.8
37.2
31.6
26.1
20.5
-
-
63.3
7.3
40.4
34.8
29.2
23.7
18.1
-
-
67 60.7
6.6
54.8
49.3
43.7
38.2
32.6
27.0
21.5
54.0
7.1
52.0
46.5
40.9
35.4
29.8
24.2
18.7
62 58.2
6.5
58.2
55.8
50.2
44.7
39.1
33.5
28.0
53.0
7.0
53.0
50.7
45.2
39.6
34.1
28.5
23.0
57 58.0
6.6
58.0
56.0
50.5
44.9
39.3
33.8
28.2
53.0
7.1
53.0
50.9
45.3
39.7
34.2
28.6
23.1
2275
72 70.7
6.8
47.7
41.2
34.6
28.0
21.4
-
-
64.6
7.4
45.2
38.7
32.1
25.5
18.9
-
-
67 62.3
6.7
59.3
54.4
47.8
41.2
34.7
28.1
21.5
55.2
7.1
55.2
51.5
44.9
38.3
31.8
25.2
18.6
62 59.6
6.6
59.6
58.5
54.9
48.3
41.8
35.2
28.6
54.1
7.1
54.1
53.0
49.6
43.0
36.4
29.9
23.3
57 59.4
6.7
59.4
58.5
55.2
48.6
42.0
35.5
28.9
54.1
7.2
54.1
53.1
49.7
43.1
36.6
30.0
23.4
2600
72 72.5
6.9
52.7
45.1
37.5
30.0
22.4
-
-
66.0
7.4
50.1
42.5
34.9
27.3
19.8
-
-
67 63.8
6.7
63.8
59.5
51.9
44.3
36.7
29.1
21.6
56.3
7.2
56.3
56.3
48.9
41.3
33.7
26.1
18.5
62 61.1
6.6
61.1
61.1
59.6
52.0
44.4
36.9
29.3
55.3
7.1
55.3
55.3
54.0
46.4
38.8
31.2
23.7
57 60.9
6.7
60.9
60.9
59.9
52.3
44.7
37.2
29.6
55.3
7.2
55.3
55.3
54.1
46.5
39.0
31.4
23.8
2925
72 73.4
6.9
57.0
48.3
39.7
31.0
22.4
-
-
66.8
7.5
54.3
45.7
37.1
28.4
19.8
-
-
67 64.6
6.7
64.6
62.5
54.8
46.2
37.6
28.9
20.3
57.0
7.2
57.0
57.0
51.8
43.2
34.6
25.9
17.3
62 61.9
6.7
61.9
61.9
61.2
52.5
43.9
35.2
26.6
55.9
7.1
55.9
55.9
55.3
46.7
38.0
29.4
20.8
57 61.7
6.7
61.7
61.7
61.2
52.6
43.9
35.3
26.7
55.9
7.3
55.9
55.9
55.4
46.7
38.1
29.5
20.8
3250
72 74.3
7.0
61.2
51.5
41.8
32.1
22.4
-
-
67.6
7.5
58.6
48.9
39.2
29.5
19.8
-
-
67 65.5
6.8
65.5
65.5
57.8
48.1
38.4
28.7
19.0
57.7
7.3
57.7
57.7
54.8
45.1
35.5
25.8
16.1
62 62.7
6.7
62.7
62.7
62.7
53.0
43.3
33.6
23.9
56.6
7.2
56.6
56.6
56.6
46.9
37.2
27.6
17.9
57 62.5
6.8
62.5
62.5
62.5
52.8
43.1
33.4
23.7
56.6
7.3
56.6
56.6
56.6
46.9
37.2
27.6
17.9
1
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.