15

Air Handling Unit and Hot Water Coil Accessory Heating Capacity

ND360 / 1HW0406, ND480 & ND600 / 1HW0407

1

1

These capacities do not include any blower motor heat.

NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.

UNIT

MODEL

HOT WATER

COIL MODEL

GPM

CFM

CAPACITY (MBH)

ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F.

70

90

110

130

150

ND360

1HW0406

50

8,000

236

304

372

440

508

10,000

265

341

416

492

568

12,000

291

374

457

540

623

14,000

315

405

495

585

675

ND480

1HW0407

75

12,800

348

447

547

646

746

16,000

389

500

611

722

833

19,200

425

547

668

790

911

ND600

75

16,000

389

500

611

722

833

20,000

436

561

686

810

935

24,000

473

610

746

882

1,019

Hot Water Coil Capacity Correction And Pressure Drop Vs GPM

1

1

For pressure drop in feet (water), multiply these values by 2.31.

HOT WATER COIL MODEL

GPM

PRESSURE DROP

PSI

CAPACITY CORRECTION

FACTOR

1HW0406

25

0.4

0.79

50

1.0

1.00

75

1.8

1.04

100

3.4

1.07

1HW0407

50

1.0

0.95

75

1.5

1.00

100

2.4

1.03

125

3.5

1.05

Advertising