York YMA024 User Manual

Page 3

Advertising
background image

036-21570-002 Rev. D (0605)

Unitary Products Group

3

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-

connecting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

Additional R-22 Charge / TXV Size for Various Matched Systems

Outdoor Unit

YMA02411

YMA03011

YMA03611

YMA04211

YMA04811

YMA06011

Unit

Orifice

(s)

63 69 78 87 -

96

Approved System Thermal Expansion Valve

1,2

1TV0701 1TV0701 1TV0702 1TV0702 1TV0703

-

Factory R-22 Charge, lbs-oz

7 - 2

7 - 12

8 - 6

8 - 12

9 - 1

14 - 2

Indoor Coil

3

Coil Orifice

4

Orifice - Additional Charge, Oz

G2FD030(S,H)17

65

63/(701) + 2

69/(701) + 0

-

-

-

G2FD035(S,H)14

65

63/(701) + 2

69/(701) + 0

-

-

-

G2FD036(S,H)17

65

-

-

78/(702) + 3

-

-

-

G2FD036(S,H)21

75

-

-

78/(702) + 5

-

-

-

G2FD048(S,H)21,24

84

-

-

-

87/(702) + 3

-

-

G2FD060(S,H)24 90

-

-

-

-

703 + 6

96 + 6

G2FD061H24 90

-

-

-

-

703 + 12

96 + 12

G1HA036H14

75

63/(701) + 8

69/(701) + 6

78/(702) + 5

-

-

-

G1HA036H17

78

63/(701) +12

69/(701) + 9

78/(702) + 8

-

-

-

G1HA048H21

84

-

-

-

87/(702) + 4

-

-

G1HA060H24 90

-

-

-

-

703 + 6

96 + 6

G1HD036

69

63/(701) + 8

69/(701) + 5

78/(702) + 5

-

-

-

G1HD048

81

-

-

-

87/(702) + 0

-

-

G1HD060 93

-

-

-

-

703 + 0

96 + 0

G1NA036S17J

67

63/(701) + 4

69/(701) + 2

78/(702) + 1

-

-

-

G1NA036S21C

67

63/(701) + 4

69/(701) + 2

78/(702) + 1

-

-

-

G1NA060S24T

87

-

-

-

87/(702) + 8

703 + 1

96 + 0

G1FA/G1UA036S14

73

63/(701) + 4

69/(701) + 2

78/(702) + 1

-

-

-

G1FA/G1UA036S17,21

73

63/(701) + 2

69/(701) + 0

78/(702) + 0

-

-

-

G1FA/G1UA048S21

84

-

-

-

87/(702) + 5

-

-

G1FA/G1UA060S21,24 90

-

-

-

-

703 + 6

96 + 6

F2RC/F2FC036

75

63/(701) + 2

69/(701) + 0

-

-

-

-

F2RP024

61

63/(701) + 0

-

-

-

-

-

F2RP/F2FP030

65

63/(701) + 2

69/(701) + 0

-

-

-

-

F2RP/F2FP036

75

-

-

78/(702) + 5

-

-

-

F2FP040

63

-

-

78/(702) + 8

-

-

-

F2RP/F2FP042

78

-

-

78/(702) + 8

-

-

-

F2FP045 78

-

-

-

-

703 + 6

-

F2FP048

84

-

-

-

87/(702) + 7

-

-

F2FP060 90

-

-

-

-

703 + 6

96 + 6

F2FV060 90

-

-

-

-

703 + 6

96 + 6

Indoor Coil with factory
installed TXV

2,4

Factory installed

coil orifice

3

Additional Charge, Oz.

G2FD030(S,H)17T -

2

0

-

-

-

G2FD035(S,H)14T -

2

0

-

-

-

G2FD036(S,H)17T -

-

-

3

-

-

-

G2FD036(S,H)21T -

-

-

5

-

-

-

G2FD060(S,H)24T -

-

-

-

-

6

-

G1HA036H14T -

-

-

5

-

-

-

G1HA036H17T -

-

-

8

-

-

-

G1HA060H24T -

-

-

-

-

6

-

G1FA/G1UA036S14T -

-

-

1

-

-

-

G1FA/G1UA036S17,21T -

-

-

0 -

-

-

G1FA/G1UA060S21,24T -

-

-

-

-

6

-

F3RP024 -

0

-

-

-

-

-

F3RP030 -

2

0

-

-

-

-

F3RP036 -

-

-

5

-

-

-

F3RP042 -

-

-

8

-

-

-

F3FP040 -

-

-

8

-

-

-

F3FP060 -

-

-

-

-

6

-

F3FV060 -

-

-

-

-

6

-

FOOTNOTES:

1

Only the TXV kits listed above are approved for use in these systems. The charge adder is the same as that listed for the orifice.

2

Models with reciprocating compressors require start kits when matched to TXV indoor coils.

3

Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit
2FD06700224.

4

These orifices or TXVs are factory mounted in the flow device of each indoor coil (701, 702, 703 indicates 1TV07…series). A “T”
suffix indicates a coil or air handler with a factory mounted TXV.