Basic setup menu, Table b-2 – Xantrex Technology SW Plus 4024 User Manual
Page 279

Basic Setup Menu
976-0043-01-02
B–5
Basic Setup Menu
provides a list of Basic Setup Menu headings and menu items,
with available set points. This table also provides the default settings for
each menu item as programmed in the factory. The last column “User
Settings” is provided for you to write in the settings specific to your
installation.
Table B-2 Basic Setup Default and User Settings for the Sine Wave Plus 2524 and 2548 Models
Sine Wave Plus
2524
Sine Wave Plus
2548
User
Settings
Basic Setup Menus
Range/
Display
Default
Range/
Display
Default
10 Time of Day Setup Menu
“10 Time of Day Setup Menu” on page 6–11
for details.
10A Set Hour
00:00:00 to
23:50:00
00:00:00
00:00:00 to
23:50:00
00:00:00
10B Set Minute
00:00:00 to
00:09:00
00:00:00
00:00:00 to
00:09:00
00:00:00
10C Set Second
00 to 59
00:00:00
00 to 59
00:00:00
11 Inverter Setup Menu
“11 Inverter Setup Menu” on page 6–12
for details.
11A High Battery Cut Out Vdc
16.1 to 34.0
32.0
32.2 to 68.0
64.0
11B Low Battery Cut In Vdc
16.1 to 33.9
26.0
32.2 to 67.8
52.0
11C Low Battery Cut Out Vdc
11.0 to 33.9
22.0
32.0 to 67.8
44.0
11D LBCO Delay Minutes
01 to 255
15
01 to 255
15
11E Search Watts (SRCH)
00 to 248
08
00 to 248
08
12 Battery Charging Menu
“12 Battery Charging Menu” on page 6–19
for details.
12A Finish Stage
SILENT
FLOAT
FLOAT
SILENT
FLOAT
FLOAT
12B Bulk Volts DC
20.0 to 32.0
28.8
40.0 to 64.0
57.6
12C Float Volts DC
20.0 to 32.0
26.8
40.0 to 64.0
53.6
12D Equalize Volts DC
20.0 to 32.0
28.8
40.0 to 64.0
57.6
12E Max Charge Amps AC
01 to 20
20
01 to 20
20
12F Bulk Done Amps AC
00 to 45
10
00 to 45
10
12G EQ Vdc Done Timer
00:00 to
23:50
02:00
00:00 to
23:50
02:00
12H Max Bulk/EQ Timer
00:00 to
23:50
05:00
00:00 to
23:50
05:00