Unit dimensions (rear view), Disconnect/blower access location, 21 utilities entry – York 60 User Manual

Page 26: 22 minimum clearances

Advertising
background image

255040-YTG-A-0506

26

Unitary Products Group

FIGURE 7 -

UNIT DIMENSIONS (REAR VIEW)

FIGURE 8 -

DISCONNECT/BLOWER ACCESS LOCA-
TION

TABLE 21: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO

1

Control Wiring

2

Side

Bottom

B

2” KO

1

Power Wiring

Side

Bottom

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

1. Opening in the bottom to the unit can be located by the

side in the insulation.

2. Do not remove the 2” knockout ring.

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

CONTROL BOX
ACCESS

A,B
WIRING ENTRY
(See Detail “B”)

MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the

blower housing inside
the blower compartment)

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER MOTOR
ACCESS

FILTER
ACCESS

DOT PLUGS

TABLE 22: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

24”

Below Unit

1

0”

Above Unit

2

72” (For

Condenser Air Discharge)

1. Units may be installed on combustible floors made

from wood or class A, B, or C roof covering material.

2. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct condenser air dis-
charge outlet.

Advertising
This manual is related to the following products:

48, 36