Table 26: minimum clearances, Unit dimensions dj180, 210, 240 & 300 (rainhood), 26 minimum clearances – York DJ 300 User Manual

Page 32

Advertising
background image

261660-YTG-D-0708

32

Johnson Controls Unitary Products

NOTE: ELEC / ELEC Models: Units and ductwork are

approved for zero clearance to combustible material
when equipped with electric heaters.

GAS / ELEC Models: A 1” clearance must be
provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the
unit.

The products of combustion must not be allowed to
accumulate within a confined space and recirculate.

Locate unit so that the vent air outlet hood is at least:

• Three (3) feet above any force air inlet located

within 10 horizontal feet (excluding those integral to
the unit).

• Four (4) feet below, four horizontal feet from, or one

foot above any door or gravity air inlet into the
building.

• Four (4) feet from electric and gas meters,

regulators and relief equipment.

FIGURE 6 - UNIT DIMENSIONS DJ180, 210, 240 & 300 (RAINHOOD)

TABLE 26: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

36”

Rear

24” (Less Economizer)

49” (With Economizer)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

3

Right Side (Cond. Coil)

36”

Below Unit

1

1.

Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.

0”

Above Unit

2

2.

Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.

3. If economizer is factory installed, the unassembled rain hood

must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.

72” With 36” Maximum

Horizontal Overhang (For

Condenser Air Discharge)

REAR VIEW

DETAIL “Y”

UNIT WITH RAIN HOODS

LH VIEW

28-3/16”

92”

36-5/8”

5”

16-1/8”

SUPPLY AIR
COMPARTMENT

POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)

ECONOMIZER
MOTORIZED
DAMPER
RAIN HOOD
(on Outdoor Air Compartment)

ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS

FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
Compartment)

1“ CONDENSATE
DRAIN
(Must be trapped)

Advertising
This manual is related to the following products: