343615-YTG-D-0708

8

Johnson Controls Unitary Products

ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.

BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.

CO

2

SENSOR - Senses CO

2

levels and automatically

overrides the economizer when levels rise above the
present limits.

COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.

HAIL GUARD - Hail Guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.

GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.

TABLE 1:

CAPACITY RATINGS - (ARI 210/240)

1

1. 80/67°F Indoor and 95°F outdoor.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling

capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).

SEER

3

3. SEER = Seasonal Energy Efficiency Ratio.

CFM

SOUND

RATING

(Db)

4

4. Rated in accordance with ARI 270 Standard.

DY036

35.6

12

14

1200

84

DY048

46.0

12

14

1600

83

DY060

5

5. Models are 3Ø only.

59.0

11.6

14

1750

81

TABLE 2:

GAS HEAT RATINGS

1

1. All units are single-stage heating.

MODEL

MBH

INPUT

MBH

OUTPUT

AFUE

(%)

TEMP

RISE ºF

DY036N04
DY036N08

50

100

40
80

80.9
80.5

15 - 45
45 - 75

DY048N06
DY048N10

75

125

60

100

80.9
80.3

25 - 70
45 - 75

DY060N08
DY060N10

100
125

80

100

80.5
80.3

25 - 55
30 - 75

TABLE 3:

2 STAGE GAS HEAT RATINGS

MODEL

1

1. Models are 3Ø only.

MBH INPUT

MBH OUTPUT

STEADY STATE EFFICIENCY

RISE

MINIMUM HEATING

AIRFLOW (CFM)

1

ST

STAGE 2

ND

STAGE 1

ST

STAGE 2

ND

STAGE

1

ST

STAGE

2

ND

STAGE

MIN.

MAX.

DY036D06

45

75

35.8

60.8

79.4

81.1

35

70

790

DY036D10

69

115

55.2

92

80.0

80.2

55

90

950

DY048D06

45

75

35.7

60.8

79.4

81.1

25

70

790

DY048D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DY060D06

45

75

35.8

60.8

79.4

81.1

20

55

1010

DY060D10

75

125

60.4

100.6

80.5

80.5

35

75

1230