Power wiring – York MV User Manual

Page 7

Advertising
background image

255427-YTG-F-1006

Unitary Products Group

7

POWER WIRING

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

Model

Heater

Model

Min. Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

Circuit

Circuit

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

MV12B

4HK165N1506

49.2 / 55.4 21.7 / 25.0

50 / 60

25 / 25

8 / 6

10 / 10

MV12D

4HK16501506

49.2 / 55.4 21.7 / 25.0

50 / 60

25 / 25

8 / 6

10 / 10

4HK16501806

45.6 / 51.2 39.7 / 45.8

50 / 60

40 / 50

8 / 6

8 / 8

4HK16502006

49.2 / 55.4 43.3 / 50.0

50 / 60

45 / 50

8 / 6

8 / 8

MV16C

4HK16501506

51.0 / 56.9 21.7 / 25.0

50 / 60

25 / 25

8 / 6

10 / 10

4HK16501806

17.3 / 52.7 39.7 / 45.8

50 / 60

40 / 50

8 / 6

8 / 8

4HK16502006

51.0 / 56.9 43.3 / 50.0

50 / 60

45 / 50

8 / 6

8 / 8

MV20D

4HK16501506

53.1 / 58.8 21.7 / 25.0

60 / 60

25 / 25

6 / 6

10 / 10

4HK16501806

49.5 / 54.6 39.7 / 45.8

50 / 60

40 / 50

8 / 6

8 / 8

4HK16502006

53.1 / 58.8 43.3 / 50.0

60 / 60

45 / 50

6 / 6

8 / 8

4HK16502506

49.3 / 56.5 43.3 / 50.0 21.7 / 25.0

50 / 60

45 / 50

25 / 25

8 / 6

8 / 8

10 / 10

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

KW & MBH CONVERSIONS

FOR

208-VOLT

OPERATION MULTIPLY

240-VOLT

TABULATED KW & MBH BY

.751

230-VOLT

240-VOLT

.918

ELECTRICAL DATA - COOLING UNIT ONLY (60 Hz)

MODEL

Total Motor Amps

Minimum Circuit Ampacity

Max. O.C.P.

1

Amps/Type

Minimum Wire Size

AWG @ 75°C

60 Hertz

60 Hertz

208V

230V

208V

230V

MV12B

4.7

4.3

5.9

5.4

15

14

MV12D

4.7

4.3

5.9

5.4

15

14

MV16C

6.1

5.0

7.6

6.9

15

14

MV20D

7.8

7.0

9.7

8.8

15

14

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

Line Power

ELECTRIC HEAT

WITHOUT CIRCUIT BREAKER

SINGLE SOURCE (2.5 - 10 KW)

GND. LUG

POWER
SUPPLY

GND.
LUG

ELECTRIC HEAT

WITHOUT CIRCUIT BREAKER

3 PHASE (10 - 15 KW)

GND. LUG

POWER
SUPPLY

GND.
LUG

1 PHASE ELECTRIC HEAT

WITH CIRCUIT BREAKER

AS SHIPPED FROM FACTORY

SINGLE SOURCE

(2.5 - 25 KW) - 25 KW SHOWN

GND. LUG

POWER
SUPPLY

GND.
LUG

1 PHASE ELECTRIC HEAT

WITH CIRCUIT BREAKER

& BREAKER BAR REMOVED

MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN

GND. LUG

POWER
SUPPLY 1

GND.
LUG

POWER
SUPPLY 2

POWER
SUPPLY 3

TYPICAL WIRING WITHOUT ELECTRIC HEAT

GND. LUG

POWER
SUPPLY

GND.
LUG

POWER WIRING (208/230-1-60)

NOTE: USE ONLY COPPER CONDUCTORS

TERMINAL
BLOCK

TERMINAL
BLOCK

MAY BE 1, 2, OR 3
CIRCUIT BREAKERS

MAY BE 1, 2, OR 3
CIRCUIT BREAKERS

(JUMPER BAR)

CONNECT LEADS WITH WIRE NUTS
(TYPICAL ALL HEAT KITS)