TABLE 7: COOLING CAPACITIES - 5 TON (DEE / DEG060)

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

85°F

95°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

kW

SENSIBLE CAPACITY

1

, MBH

TOTAL

CAP

.1

MBH

POWER

INPUT

2

kW.

SENSIBLE CAPACITY

1

, MBH

ENTERING DRY BULB, °F

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

2500

72

75

4.6

53

46

38

31

23

-

-

73

5.0

53

46

38

31

23

-

-

67

67

4.5

64

56

49

41

34

26

19

65

4.9

64

56

49

41

34

26

19

62

62

4.5

62

62

62

54

47

39

32

60

4.9

60

60

60

53

46

38

31

57

56

4.4

56

56

56

48

41

33

26

55

4.8

55

55

55

47

40

32

25

2250

72

74

4.6

51

44

37

31

24

-

-

72

5.0

50

43

37

30

23

-

-

67

67

4.5

62

55

48

42

35

28

21

64

5.0

61

54

47

41

34

27

20

62

61

4.5

61

61

61

54

47

40

34

59

4.9

59

59

59

52

45

38

32

57

55

4.4

55

55

55

48

41

35

28

53

4.8

53

53

53

46

39

33

26

2000

72

73

4.5

49

43

37

31

25

-

-

70

5.0

47

41

35

29

23

-

-

67

66

4.5

60

54

48

42

36

30

24

63

5.0

58

52

46

40

34

28

22

62

60

4.4

60

60

60

54

48

42

36

58

4.9

58

58

57

51

45

39

33

57

55

4.4

55

55

54

48

42

36

30

52

4.8

52

52

61

45

39

33

27

1750

72

72

4.5

45

40

34

29

24

-

-

68

5.0

43

38

33

27

22

-

-

67

65

4.5

55

50

44

39

34

29

23

61

4.9

53

47

42

37

32

26

21

62

60

4.4

60

59

56

50

45

40

35

56

4.9

56

56

53

48

42

27

32

57

54

4.4

54

53

50

45

40

34

29

50

4.8

50

50

48

42

37

32

27

1500

72

71

4.5

41

37

32

27

23

-

-

66

5.0

40

35

30

26

21

-

-

67

63

4.5

50

46

41

36

32

27

22

58

4.9

48

43

39

34

29

25

20

62

59

4.4

59

57

52

47

43

38

34

54

4.9

54

54

49

44

40

35

31

57

53

4.4

53

52

47

42

38

33

28

49

4.8

49

49

44

40

35

30

26

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

105°F

115°F

TOTAL

CAP

.1

MBH

POWER

INPUT

2

kW.

SENSIBLE CAPACITY

1

, MBH

TOTAL

CAP

.1

MBH

POWER

INPUT

2

kW.

SENSIBLE CAPACITY

1

, MBH

ENTERING DRY BULB, °F

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

2500

72

66

5.5

51

44

36

29

21

-

-

60

6.0

49

41

34

26

19

-

-

67

59

5.5

58

54

46

39

31

24

16

53

6.0

53

51

43

36

28

21

13

62

55

5.4

55

55

55

47

40

32

25

49

5.9

49

49

49

42

34

27

19

57

49

5.4

49

49

49

42

35

27

20

44

5.9

44

44

44

37

29

22

15

2250

72

65

5.5

48

42

35

28

21

-

-

58

6.0

46

40

33

26

20

-

-

67

58

5.5

57

52

45

38

31

25

18

52

6.0

52

49

43

36

29

22

16

62

54

5.4

54

54

54

48

41

34

28

48

5.9

48

48

48

44

37

30

24

57

48

5.4

48

48

48

42

36

29

22

44

5.9

44

44

44

39

32

25

19

2000

72

63

5.5

45

39

33

28

22

-

-

57

6.0

44

38

32

26

20

-

-

67

58

5.5

55

50

44

38

32

26

20

52

6.0

52

48

42

36

30

24

18

62

52

5.4

52

52

52

48

42

36

30

47

5.9

47

47

47

46

40

34

28

57

47

5.4

47

47

47

43

37

31

25

43

5.9

43

43

43

41

35

29

23

1750

72

62

5.5

42

36

31

26

21

-

-

55

6.1

40

35

30

24

19

-

-

67

55

5.5

50

45

40

35

30

24

19

50

6.0

48

43

38

33

28

22

17

62

51

5.4

51

51

50

45

40

35

29

46

6.0

46

46

46

43

37

32

27

57

46

5.4

46

46

45

40

35

30

24

41

5.9

41

41

41

38

33

27

22

1500

72

60

5.5

38

33

29

24

19

-

-

53

6.1

36

32

27

23

18

-

-

67

53

5.5

46

41

37

32

27

23

18

47

6.1

44

39

35

30

25

21

16

62

49

5.4

49

49

47

42

37

33

28

44

6.0

44

44

44

39

35

30

25

57

44

5.4

44

44

42

37

33

28

23

40

6.0

40

40

40

35

30

26

21

1.

These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 10 or 11, multiply
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2.

These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
motor power input is 0.36kW. Refer to Tables 10 or 11 for the kW of the supply air blower motor.