TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - DEE/DEG036-060 W/ DIRECT DRIVE

1

MODEL

DEE/DEG

MOTOR

SPEED

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

2

0.20

0.30

0.40

0.50

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

036

HI

-

-

-

-

1699

825

1650

785

MED

1684

800

1631

780

1582

750

1524

720

LOW

1487

710

1464

690

1421

670

1367

650

048

HI

1996

960

1933

936

1868

910

1795

880

MED

1804

838

1765

810

1714

785

1650

765

LOW

1681

760

1640

738

1604

715

1541

695

060

HI

2400

1155

2338

1125

2274

1095

2167

1045

MED

2290

1105

2214

1065

2145

1030

2071

990

LOW

2150

1020

2100

990

2029

950

1965

910

MODEL

DEE/DEG

MOTOR

SPEED

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

1

0.6

0.70

0.80

0.90

1.00

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

CFM

WATTS

036

HI

1570

755

1430

725

1360

700

1280

680

1180

655

MED

1410

690

1324

650

1260

630

1185

610

1100

590

LOW

1315

620

1246

605

1185

590

1110

570

1020

545

048

HI

1722

845

1635

820

1544

790

1419

765

1300

740

MED

1589

735

1508

705

1407

675

1306

645

1195

625

LOW

1490

670

1416

645

1337

620

1230

595

1120

575

060

HI

2096

1010

1990

980

1887

945

1771

905

1629

855

MED

1990

950

1911

920

1828

885

1724

835

1604

798

LOW

1905

880

1816

838

1724

800

1644

770

1531

710

1.

Side Duct application (230/460/575 Volts)

2.

Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance val-
ues on applications other than gas / electric units with side duct airflows.

TABLE 12: STATIC RESISTANCES

DESCRIPTION

RESISTANCE, IWG

CFM

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

ECONOMIZER

1

2

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

ELECTRIC HEATERS

1

5 - 15 kW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

20 - 30 kW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

BOTTOM DUCT CONNECTIONS

1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

COOLING ONLY

3

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1.

Deduct these resistance values from the available external static pressure shown on Tables 8, 9, 10, and 11.

2.

The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

3.

Add these resistance values to the available static resistance in the respective Blower Performance Table (see Tables 8, 9, 10,
and 11).

Advertising
This manual is related to the following products: