York 090 User Manual

Page 3

Advertising
background image

279104-YTG-B-0307

Unitary Products Group

3

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon-

necting line tubing.

2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaportor + adder for line set.

5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.

Additional R-22 Charge / Orifice Size for Various Matched Systems

Outdoor Unit

E1RA036S(25,46)

E1RA048S(25,46)

E1RA060S(25,46)

Unit Orifice (s)

1

71, 81

81, 84, 87

99

Factory R-22 Charge, lbs-oz

5 - 12

8 - 3

11 - 3

Indoor Coil

System Orifice = Additional Charge, Oz

FC/MC/PC35(B,C)3X

81 + 8

FC/MC/PC/UC36(A,B,C)3X

71 + 7

FC/MC/PC/UC42(B,C)3X

81 + 8

FC/MC/PC/UC48C3X

87 + 6

FC/MC/PC/UC48D3X

87 + 6

FC/MC/PC/UC60C3X

84 + 4

99 + 0

FC/MC/PC/UC60D3X

84 + 4

99 + 0

AHP36C3X

81 + 13

84 + 3

AHP42C3X

81 + 13

84 + 3

AHP/SHP48D3X

84 + 4

99 + 0

AHP60D3X

84 + 4

99 + 0

G1NA036S17L

71 + 7

G1NA048S21D

71 + 7

81 + 8

G1NA048S24P

81 + 8

G1UA048S21/24

81 + 13

84 + 3

G1UA060S24

84 + 4

99 + 0

G1FA048S21/24

81 + 13

84 + 3

G1FA060S24

84 + 4

99 + 0

G2FD042S21

81 + 8

G2FD048S21/24

87 + 6

G2FD060S24

84 + 4

99 + 0

FOOTNOTES:

1. These orifices are packed in the instruction/warranty packet of each outdoor unit.

Advertising
This manual is related to the following products: