Wwarning w warning – 3M MACURCO GD-6 User Manual

Page 7

Advertising
background image

10

11

GD-6

Main Fan Power

120VAC

ALARM

120VAC

Power

Exhaust Fans

coil

coil

power

output

GD-6

+

power

output

+

8

7

6

5

4

4

3

3

2

2

1

1

1

1

3

3

4

5

6

7

8

9

2

24 V

RET

N.C.

N.C.

N.C.

N.O.

N.O.

N.O.

COM

COM

COM

-1 LOOP

+1 LOOP

+24 VDC

-1 LOOP

+1 LOOP

+24 VDC

- Strobe

+ Strobe

- Horn

+ Horn

Relay 1

Gnd

Panel Power

120/250VAC

3M™ MACURCO™

DETECTION AND VENTILATION

CONTROL PANEL DVP-120

STARTER RELAYS

120VAC COILS

Relay 2

Relay 3

24 V

RET

L

N

Typical Connection to the 3M™ Macurco™ Detection and Ventilation
Control Panel DVP-120

Gas detection and exhaust fan control is provided by a 3M™ Macurco™ DVP-120 system. This System
will use the GD-6 Combustible Gas to current transducer, Nitrogen Dioxide to current transducers or
Carbon Monoxide to current transducers. Each transducer will measure the level of the target gas and
provide this information to the DVP-120 over a 4-to-20mA current loop.
All power and signal connections for the transducers are provided from the DVP-120 control panel, via
unshielded four conductor cable. The DVP-120 control panel provides three relays which can be used for
ventilation fan control or alarm signaling. These relays (SPDT-Form C) are for pilot duty only, capable of
switching 10 amps loads up to 240VAC.
NOTE:
1. Power connections at the sensor are non-polarized.

power Up

W

WarnInG

W

WarnInG

Each time the unit is turned on it performs a self-test, which activates visual alarms. If the self-test fails, or if all the alarms

do not activate, do not use. Failure to do so may adversely affect product performance and

result in sickness or death.

The 3M™ Macurco™ GD-6 Combustible Gas Detector cycles through an internal self-test cycle for the first minute that it is

powered. The unit will execute the test cycle any time power is dropped and reapplied (i.e. power failure). During the self-test

cycle the unit will display the firmware version number, then count down from 60 to 0 and finally go into normal operation. The

fan and alarm relay will be activated for the power-up cycle unless the “Power Up Test” (PUt) option is OFF. The indicator light

(LED) will flash green during the self-test cycle. At the end of the 1 minute cycle, the unit will take its first sample of the air and

the light will turn solid green.

Do not cover or obstruct visual alarm LED. Doing so may adversely affect product performance and

result in sickness

or death.

operation

1. With the display function turned “On”, the 3M™ Macurco™ GD-6 Combustible Gas Detector will show the current

concentration of gas % LEL or “0” (zero) in clean air. When the gas concentration reaches the Fan Relay setting (10% LEL,

for example) the display will flash back and forth between “FAn” and “10”. With the display function turned ”Off”, the

display does not show the gas concentration, but will show “FAn” as long as the fan relay is activated.

2. With the display function turned “On” and the gas concentration reaching the alarm relay setting, (20% LEL, for example)

the display will flash back and forth between “ALr” and “20”. The buzzer will sound indicating “Alarm” if the buzzer is

turned “On”. With the display function turned off the display does not show the gas concentration, but will show “ALr”

when the Alarm relay is activated.

3. With the 4-20mA function turned “On”, the 4-20mA output will correspond to the concentration (0-50% LEL). The display

will show “FAn” and “ALr” and sound as outlined above.

Default Configuration – Factory Settings

• The default

Display setting is off

• The default

power Up Test setting is on

• The default

Buzzer setting is off

• The default

alarm relay setting is activation at 20% LEL

• The default

Fan relay Delay setting is 3 minutes

• The default

Fan Minimum runtime setting is oFF

• The default

Fan relay setting is activation at 10% LEL

• The default

alarm relay Configuration is normally open

• The default

4-20ma output setting is oFF

Advertising