Minimum damper shaft length, Standard, Optional – Schneider Electric MS40-717X User Manual

Page 3: Position indicator, Nominal damper area, Direction of rotation, Environment, Ambient temperature limits, Shipping & storage, Operating

Advertising
background image

F-26748-6

© Copyright 2010 Schneider Electric All Rights Reserved.

3

Minimum Damper Shaft Length,

Standard Damper shaft must be at least 4-5/8" (117 mm) long for standard mounting.
Optional Shorter than standard length shafts require the AM-676 shaft extension
(order separately).

Position Indicator, Scale numbered from 0 to 95°, provided for position indication.
Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specifications.
Direction of Rotation, Clockwise or counterclockwise rotation is determined by
actuator mounting. The zero (0) position on the position indicator is the normal or spring
return position.

Environment

Ambient Temperature Limits:

Shipping & Storage, -40 to 160°F (-40 to 71°C).
Operating, -25 to 140°F (-32 to 60°C).

Humidity: 5 to 95% RH, non-condensing.
Location: NEMA 1. NEMA Type 4 (IEC IP56) with customer supplied water tight conduit
connectors.

Agency Listings

UL 873: Underwriters Laboratories Inc. listed (File # E9429 Category Temperature-
Indicating and Regulating Equipment).
CUL: UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards
C22.2 No. 24-93.
European Community: EMC Directive (2004/188/EC). Low Voltage Directive
(72/23/EEC). See Table-1 for specific models.
Australia: This product meets requirements to bear the C-Tick Mark according to the terms
specified by the Communications Authority under the Radiocommunications Act 1992.

Table-1 Model Chart.

ACCESSORIES
AM-620

Remote mount single/dual damper actuator kit

AM-621

Round damper shaft extension kit (1/2" ID x 1" OD) for dual actuator mounting

AM-703

Span adjustment

AM-704

Modulation Interface, converts a PWM to 2 to 10 Vdc

AM-705

Positioner, remote/minimum positioning

AM-706

Positioner, flush mount digital position indicator

AM-707

Digital Indication

AM-708

Resistor for 500

Ω modulating signal conversion

AM-751

Standard anti-rotation bracket 9" long x 13/16" wide (229 x 21 mm), included with
actuator

AM-752

Optional anti-rotation bracket 4" long x 1-11/6" wide (102 x 43 mm), for narrow
spaces

AM-753

Optional universal mounting clamps for 5/8"(16 mm) square shaft, 3/4" and 1"
(19 to 25 mm) round shafts (two per package)

AM-754

Standard universal mounting clamps for 3/8" to 1/2" (10 to 13 mm) round and
square shafts, two included with actuator

AM-756

Metric conduit adaptor M20 x 1.5 to 1/2" NPT (two per package)

AV-607

Dual mount rack and pinion valve linkage kit for 2-1/2" through 5" VB-8xxx series
valve bodies and 2-1/2" to 4" VB-9xxx series valve bodies except VB-9323

AV-609

Dual mount rack and pinion valve linkage kit for 6" VB-8xxx series valve bodies and
5" and 6" VB-9xxx series valve bodies except VB-9323

TF-711-02

1/2" Sealtight water tight conduit connector (straight)

TF-713-02

1/2" Sealtight water tight conduit connector (90°)

X-5521

1/2" Pipe plug, included with actuator

Part

Number

Actuator Power Input

Approximate 93° Rotation

Timing in Seconds @ 70° F

(21°C) for Rated Torque

Output Torque Rating

lb.-in. (N-m)

Voltage

Hz

Running

Watts

VA

Running

Holding

Powered

Spring

Return

Minimum

Maximum Stall

MS40-7173

24 Vac ±20%

50 60

5.5

7.8

4.7

147

65

150 (17)

a

a

Approximate 2% torque derating per 1°F above 122°F in the drive direction.

545 (61.8)

22-30 Vdc

5.0

5.6

2.5

MS40-7170

120 Vac ±10%

50 60

6.4

8.5

5.2

MS40-7171

240 Vac ±10%

7.2

10.8

9.0

Advertising