INSTALLATION

Inspection

Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return
damaged products.

Requirements

Job wiring diagrams

Tools (not provided)

– Socket wrench 1/2 inch, used for universal mounting clamp nuts
– Open-end wrench 10 mm, used for installing AM-676 universal shaft extension
– Slotted screwdriver, used for installing anti-rotation brackets
– Allen wrench 3/16", used for manual override

Appropriate accessories

– Water tight 1/2 inch conduit seals TAC part number TF-711-02 or T&B #5332

(straight, TAC part number TF-713-02 or T&B #5352 (90°), or equivalent.

– Water tight 1/2 inch flexible conduit (e.,g. Anaconda: Sealtight) or 20 mm flexible

water tight conduit when using AM-756 metric conduit adapter with appropriate
metric water tight seals.

– Water tight 1/2" flexible conduit (Anaconda: Sealtight) or 20 mm flexible water tight

conduit when using AM-756 metric conduit adaptor

– Two #8 1/2" (13 mm) sheet metal screws for mounting (optional)

Training: Installer must be a qualified, experienced technician

4 to 20 mA DC

Controller

(+) 4 to 20 mA DC

(-) Common DC

Power

GRD

GRD

1

1

2

MS40-717X

MS40-717X

1 Unused conduit port must remain plugged with a

water tight pipe plug as shipped from factory to
maintain NEMA Type 4 or IP56 rating.

2 See table for power wire designations.

3 Both actuators must be set to operate in the same

direction.

Yellow/Black

AI

Gray

Blue

AO

Yellow/Black

AI

Gray

Blue

AO

Position Feedback (-)

Signal 2 to 10 Vdc (+)

COM

COM

3

3

4

4

4 Color coding of wiring on older models (MX40-717x-0-

0-0) manufactured prior to December, 2007, differs
from current models. See Table 4 on page 14. Consult
label on product to confirm wiring codes.

5 Keep AI, COM and AO wiring less than 30 meters

length to meed CE requirements.

5

5

Green/Yellow

Green/Yellow

500 Ohm

Figure-8 Typical 4 to 20 mAdc Control Wiring For Two Actuators On The Same Damper Shaft.

Power Wiring Identification.

Voltage

Designation

Wire Color

24 Vac or

22-30 Vdc

24H (DC+)

Red

24G (DC-)

Black

120 Vac

L1

Black

L2

White

240 Vac

L1

Brown

L2

Light Blue