Installation, Inspection, Requirements – Schneider Electric MS40-717X User Manual

Page 7: Installation inspection

Advertising
background image

F-26748-6

© Copyright 2010 Schneider Electric All Rights Reserved.

7

INSTALLATION

Inspection

Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return
damaged products.

Requirements

•

Job wiring diagrams

•

Tools (not provided)

– Socket wrench 1/2 inch, used for universal mounting clamp nuts
– Open-end wrench 10 mm, used for installing AM-676 universal shaft extension
– Slotted screwdriver, used for installing anti-rotation brackets
– Allen wrench 3/16", used for manual override

•

Appropriate accessories

– Water tight 1/2 inch conduit seals TAC part number TF-711-02 or T&B #5332

(straight, TAC part number TF-713-02 or T&B #5352 (90°), or equivalent.

– Water tight 1/2 inch flexible conduit (e.,g. Anaconda: Sealtight) or 20 mm flexible

water tight conduit when using AM-756 metric conduit adapter with appropriate
metric water tight seals.

– Water tight 1/2" flexible conduit (Anaconda: Sealtight) or 20 mm flexible water tight

conduit when using AM-756 metric conduit adaptor

– Two #8 1/2" (13 mm) sheet metal screws for mounting (optional)

•

Training: Installer must be a qualified, experienced technician

4 to 20 mA DC

Controller

(+) 4 to 20 mA DC

(-) Common DC

Power

GRD

GRD

1

1

2

MS40-717X

MS40-717X

1 Unused conduit port must remain plugged with a

water tight pipe plug as shipped from factory to
maintain NEMA Type 4 or IP56 rating.

2 See table for power wire designations.

3 Both actuators must be set to operate in the same

direction.

Yellow/Black

AI

Gray

Blue

AO

Yellow/Black

AI

Gray

Blue

AO

Position Feedback (-)

Signal 2 to 10 Vdc (+)

COM

COM

3

3

4

4

4 Color coding of wiring on older models (MX40-717x-0-

0-0) manufactured prior to December, 2007, differs
from current models. See Table 4 on page 14. Consult
label on product to confirm wiring codes.

5 Keep AI, COM and AO wiring less than 30 meters

length to meed CE requirements.

5

5

Green/Yellow

Green/Yellow

500 Ohm

Figure-8 Typical 4 to 20 mAdc Control Wiring For Two Actuators On The Same Damper Shaft.

Power Wiring Identification.

Voltage

Designation

Wire Color

24 Vac or

22-30 Vdc

24H (DC+)

Red

24G (DC-)

Black

120 Vac

L1

Black

L2

White

240 Vac

L1

Brown

L2

Light Blue