2. Connect terminals 14 and 16 to an

ohmmeter

.

3. Turn screw

until the cam

switches

the end switch

and the ohmmeter

shows 0 Ω.

The end switches are adjusted.

Dismounting of Valve and
Actuator

11

DANGER!

Danger of injury by steam or hot water!

Valve without actuator is open

, sealing

is in the actuator.

It is absolutely necessary to depressurize
system prior to dismounting.

Carry out dismounting in reverse order as
mounting.