Technical specifications – Bosch FAS-420-TM Series Aspirating Smoke Detectors LSN improved version User Manual

Page 31

Advertising
background image

FAS-420-TM | FAS-420-TM-R | FAS-420-TM-RVB

en

31

Bosch Sicherheitssysteme GmbH

F.01U.088.879 | 4.0 | 2010.12

Technical Specifications

LSN power supply

15 V DC-33 V DC

Auxiliary power supply

15 V DC-30 V DC

LSN current consumption

6.25 mA

Current consumption from auxiliary power
supply

Fan voltage

9 V

10.5 V

12 V

-

Starting current

150 mA

-

In standby

105 mA

125 mA

145 mA

-

With alarm, device variants FAS-420-TM and
FAS-420-TM-R

110 mA

130 mA

150 mA

-

With alarm, device variant FAS-420-TM-RVB

140 mA

160 mA

180 mA

Max. wire gauge

2.5 mm²

Housing material

Plastic (ABS)

Housing color

Papyrus white (RAL 9018)

Protection category according to EN 60529

-

Without air return

IP 20

-

With pipe section 100 mm/pipe bend

IP 42

-

With air return

IP 54

Permissible temperature range

-

FAS-420-TM Series Aspirating Smoke
Detectors

-20 °C to +60 °C

-

PVC pipe system

-10 °C to +60 °C

-

ABS pipe system

-40 °C to +80 °C

Permissible relative humidity (non-condensing)

Max. 95%

Sound power level (at 9 V fan voltage)

40 dB(A)

Response sensitivity (light obscuration)

0.5 to 2.0%/m

Life cycle of fan (at 12 V and 24 °C)

60,000 hrs

Advertising