Hardwiring the ups input – Dell UPS 5600R User Manual

Page 18

Advertising
background image

16

|

Installation and Startup

Hardwiring the UPS Input

WARNING:

Only qualified service personnel (such as a licensed electrician) shall perform the electrical

installation. Risk of electrical shock.

The UPS requires a dedicated branch circuit that meets the following requirements:

S

The protection device requires a two-pole disconnection device between the UPS output and the
load (see Figure 4)

S

The breaker must be wall-mounted and be readily accessible to the operator

S

For Europe, the breaker must meet the IEC/EN 60934 standard and have a contact air gap of at
least 3 mm

S

200–240 Vac

S

Single-phase

-

5600W/208V model is phase-to-phase

-

5600W/230V model is phase-to-neutral

S

50/60 Hz

S

Flexible metal conduit (recommended for ease of service and maintenance)

AC Mains

Wall

2-pole

Breaker

UPS

Line

Neutral/L2

Figure 4. Circuit Breaker Diagram