Dell Basic Rack Power Distribution Unit—Product Overview and Specifications

Product Overview and Specifications

The Dell Basic Rack PDU distributes power to the devices in the rack.

O

U T L E T S

— The Rack PDU has twelve (12) 5-15 R outlets.

P

O W E R

C O R D

— The Rack PDU has a IEC-320 C20 inlet and can be used with a detached power cord (not provided).

H553N

Electrical

Input connection

IEC-320 C20 inlet

Acceptable input voltage

100–120 VAC

±

10%

Maximum input current (phase)

15 A (12 A UL(C-UL) derated)

Input frequency

50/60 Hz

Output voltage

100–120 VAC

±

10%

Output connections

(12) 5-15 R

Maximum output current (outlet)

5-15 R; 12 A (UL(C-UL) derated)

5-15 R; 15 A (PSE)

Maximum output current (phase)

15 A (12 A UL(C-UL) derated)

Physical

Dimensions
(H x W x D)

52.29 x 5.58 x 4.69 cm
(20.59 x 2.20 x 1.85 in)

Shipping dimensions
(H x W x D)

61.21 x 12.29 x 10.66 cm
(24.10 x 4.84 x 4.20 in)

Weight

1.25 kg (2.75 lb)

Shipping weight

1.6 kg (3.52 lb)

Environmental

Maximum elevation

(above MSL)

Operating

Storage

0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)

Temperature

Operating

Storage

0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)

Humidity

Operating

Storage

5 to 95%, non-condensing
5 to 95%, non-condensing

Compliance

Safety approvals

UL(C-UL), PSE

ROHS

Dell 6T198
EU DIRECTIVE 2002/95/EC–latest revision

Advertising