Product specifications – Dell Managed PDU LED User Manual

Page 2

Advertising
background image

2

Dell Managed Rack Power Distribution Unit—Product Specifications

Product Specifications

The Dell Managed Rack PDU distributes power to the devices in the rack.
O

UTLETS

— The Rack PDU has twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19 outlets.

P

OWER

CORD

— The 3.0 m (10 ft) power cord terminates

with a 32 A, IEC-309 5-pin plug [530P6W/532P6W (Intl/NA)].

K539N

Electrical

Input connection

32 A, IEC-309 5-pin plug

Acceptable input voltage

380 - 415 VAC +6%, -10%, 3-phase

Maximum input current (phase)

32 A International; 24 A UL, C-UL (derated)

Input frequency

50/60 Hz

Input power

22.1 kVA International

17.2 UL, C-UL (derated)

Output voltage

220 - 240 VAC (Line-to-Neutral)

Output connections

Twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19

Maximum output current (outlet)

IEC-320-C13: 10 A; IEC-320-C19: 16 A International
IEC-320-C13: 12.8 A; IEC-320-C19: 12.8 A UL, C-UL

Maximum output current (phase)

32 A International; 24 A UL, C-UL (derated)

Maximum output current (breaker)

16 A International;

12.8 A UL, C-UL (derated)

Overload protection (internal)

Six (6) 16 A, 1-pole hydraulic-magnetic circuit breakers

Physical

Dimensions
(H x W x D)

182.9 x 5.6 x 5.5 cm
(72.0 x 2.2 x 2.16 in)
Depth at breakers: 9.4 cm (3.7 in.)

Shipping dimensions
(H x W x D)

207.9 x 22.5 x 15.6 cm
(81.9 x 8.9 x 6.1 in)

Weight

8.9 kg (19.5 lb)

Shipping weight

10.7 kg (23.5 lb)

Environmental

Maximum elevation

(above MSL)

Operating

Storage

0 to 3 048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)

Temperature

Operating

Storage

0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)

Humidity

Operating

Storage

5 to 95%, non-condensing
5 to 95%, non-condensing

Advertising