Dished tank top, Open vessels – VEGA VEGASON 54P…56P Profibus PA User Manual

Page 18

Advertising
background image

18

VEGASON 54P … 56P

Open vessel

Min. meas.
distance

Dished tank top

On dished tank tops, please do not mount
the instrument in the centre or close to the
vessel wall, but approx. ½ vessel radius from
the centre. Dished tank ends can act as
paraboloidal reflectors. If the transducer is
placed in the focal point of the parabolic tank,
the ultrasonic sensor receives amplified false
echoes. The transducer should be mounted
outside the focal point. Parabolically amplified
echoes can be thereby avoided.

Mounting and installation

Reference plane

< 100 mm

VEGASON 54 on dished tank top; applies also to
VEGASON 55

Reference plane

½ vessel radius

< 400 mm

VEGASON 56 on dished tank top

Reference plane

1

/

2

vessel radius

Open vessels

On open vessels, the sensors can be readily
installed on extended mounting brackets.
Mount the low-weight sensor onto such a
bracket and ensure a sufficient distance from
the vessel wall.

Min. meas.
distance

Reference plane

Advertising