2 connection plics® sensor – VEGA Remote parameter adjustment and remote maintenance User Manual

Page 3

Advertising
background image

2 Connection plics® sensor

With this version, connection of VEGACONNECT 3 is carried out via
the I²C interface integrated in the sensor. This is the easiest and
fastest way to make a connection. The housing cover of the sensor
cannot be closed when VEGACONNECT 3 is connected.

Note:
Use this connection variant only if the connection is to be short-term, in
a dry environment and not in an Ex-area.

5

6

2

3

1

4

Fig. 2: Connection plics

®

series via I²C interface

1

Analogue telephone connection (not applicable in case of GSM radio
modem)

2

Standard analogue modem or GSM radio modem

3

Special cable, art. no.: MODEM.KX

4

VEGACONNECT 3

5

I²C adapter (in the scope of delivery of VEGACONNECT 3)

6

Sensor from the plics® serie

With this version, connection of VEGACONNECT 3 is carried out via
the HART protocol and the supply cable of the sensor. Hence, the
connection can be made at any point between power supply/
processing system and sensor.

This version can also be used for connection in Ex-areas. The modem
and VEGACONNECT 3 themselves must not be located in Ex-area.

If the resistance of the connected processing system is less than
230 Ω, the digital adjustment signal is extremely damped or short-
circuited. Digital communication with the PC is then no longer possible.
With low impedance processing systems, a resistance of approx.
230 Ω must be integrated into the 4 … 20 mA connection cable. The
connection can be either carried out in parallel to the sensor or via the
resistor.

Connection to the sen-
sor (I²C)

Connection to cable
(HART)

Remote parameter adjustment and remote maintenance • Configuration and connection

3

2 Connection plics® sensor

23051

-

EN

-090302