Fms planning – VEGA VEGACOM 557 Profibus FMS User Manual

Page 26

Advertising
background image

26

VEGACOM 557 Profibus FMS

Setup

The data are actualized with function key F7.

SINEC-NCM (END)

Network - Network adjustment

————————————————————————————————————————

Network data file

: C : MESSWNCM.NET

Destination data file

:

Algorithm

: STANDARD

F

F

F

F

F

F

F

F HELP

1

2

3

4

5

6

7 TAKE OVER 8 CHOICE

FMS planning

During FMS planning, the communication relationship list KBL is defined. For control of the
selection and the time of the communication services to be furnished from CP5431 through the
S5 user program, the acyclical data traffic has to be planned. Only through this will the con-
sistency of the read in measured values be ensured during a program processing cycle.

1. CP connection planning: Edit –> Connections –> FMS connections

Kind of connection:
- MSAZ: acyclical Master-Slave connection.

Monitoring interval:
- Acyclical connections can be monitored by the CP5431. The transmission interval time is

calculated from the entered transmission interval multiplied by 10 ms. The value 0 means: no
monitoring.

SSNR:
- The interface number SSNR is the tile number of the CP forming the interface between CPU

and CP. The interface number must be unique for all orders via one connection and is there-
fore entered only once, the adjustment range is 0 …3.

ANR:
- Order number. Note: odd order numbers (1 and 3) are client orders. They must be en-

quired with a SEND handling component (stating the respective ANR/ANZW).