2 Technical Information

2.8

Connection examples for overvoltage arresters

Vessel without cathodic tank protection

to potential
equalization line

min. 4 mm

2

Cu

External earth terminal

either
overvoltage arrester

d30
d32

Note:
- Suitable cable must be used, either with metal cover (or screen). If a

cable with metal cover or screen is used (as on above figure), a potential
equalization along the entire length of the intrinsically safe circuit is not
necessary. Screen or metal cover must only be connected to the
overvoltage arrester.

- The current load capacity of the screen must correspond at least to that

of a 1,5 mm

2

Cu-line.

Earth- / PA-
connection terminal

Outer isolation

Outer isolation

Screen

Screen

Ex-area

Not Ex-area
(control room)

1

E2

E2

E1

E1

A2

A2

A1

A1

A1

A2

A2

A1

E2

E2

E1

E1

2

1
2

Typ

B62-27

Typ

B62-27

Typ

B62-27G

Typ

B62-27G

Overvoltage arrester

min. 4 mm

2

Cu

Screen

VEGATROL 20
System sensor

either
overvoltage arrester

d30
d32

Note:
- Suitable cable must be used with metal cover (or screen). Screen or

metal cover must only be connected to the overvoltage arrester.
Screen or metal cover must not be earthed.

- The cable must have an outer isolation.
- The current load capacity of the screen must correspond at least to that

of a 1,5 mm

2

Cu-line.

Earth- / PA
connection terminal

Outer isolation

Ex-area

Not Ex-area
(control room)

Vessel with cathodic tank protection

Screen

Line length

50 m

Overvoltage arrester
Type B 62 - 27 Ex 0-2
or B 62 - 27 Ex-2

Overvoltage arrester

VEGATROL 20
System sensor

117/4 A Ex
or
115 A Ex

E86 Ex

Line length

50 m

Overvoltage arrester
Type B 62 - 27 Ex 0 - 2
or B 62 - 27 Ex - 2

VEGATOR
526 W Ex

VEGATOR
526 W Ex

117/4 A Ex
or
115 A Ex

E86 Ex

Outer isolation

External earth
terminal

Cathodic tank protection
2 … 24 V
(object voltage)

intrinsically safe
circuit to signal
conditioning
instrument

intrinsically safe
circuit to signal
conditioning
instrument

Metal housing isolated or
plastic housing

Metal housing isolated or
plastic housing